UL845-style motor control center lineup with modular starter, feeder, drive, and control sections for industrial motor applications.

UL845 Motor Control Centers Explained: Standards, Components, Applications, and Selection Guide

Quick Answer

A UL845 motor control center, commonly called an MCC, is a floor-standing electrical assembly that groups motor control, motor protection, power distribution, automation, and monitoring equipment into one coordinated lineup.

A typical MCC may contain:

  • Main incoming devices
  • Horizontal and vertical busbars
  • Combination motor starters
  • Motor circuit protectors
  • Contactors and overload relays
  • Variable frequency drives
  • Soft starters
  • Feeder circuit breakers
  • Control transformers
  • PLC and communication equipment
  • Removable or fixed motor-control units

UL845 is the principal North American product standard for motor control centers. Its current published scope covers qualifying AC and DC MCCs rated up to 1,000 V and intended for installation under the applicable U.S., Canadian, or Mexican electrical codes. The standard’s scope also addresses complete MCCs used on circuits with available short-circuit current up to 200,000 A under the stated conditions.

In simple terms:

A switchboard primarily distributes power. An industrial control panel primarily controls a machine or process. A motor control center centralizes the distribution, protection, starting, stopping, speed control, and monitoring of multiple motors.

The final MCC configuration depends on the motor list, starting method, full-load current, available fault current, process logic, communication requirements, maintenance strategy, installation environment, and required certification pathway.

* *

Introduction

Motors are among the most common electrical loads in industrial facilities.

They operate:

  • Pumps
  • Fans
  • Compressors
  • Conveyors
  • Mixers
  • Crushers
  • Blowers
  • Cooling towers
  • Material-handling systems
  • Process equipment

When a facility contains only one or two motors, individual starters or control panels may be sufficient.

When a project contains many motors, however, installing separate disconnects, starters, overload devices, control transformers, wiring enclosures, and communication devices throughout the facility can increase installation complexity, cable length, maintenance effort, and floor-space requirements.

A motor control center centralizes many of these functions into a coordinated modular assembly.

Schneider Electric describes low-voltage MCCs as a compact method of grouping motor control, automation, and power distribution. Rockwell Automation similarly describes modern MCCs as modular systems that can be customized through vertical sections, motor-control buckets, communications, and application-specific components.

An MCC may therefore serve as the connection point between:

  • The upstream electrical distribution system
  • Individual motors and related loads
  • The plant control system
  • Operators and maintenance personnel
  • Facility monitoring and communication networks

Understanding this role is essential because an MCC is not simply a large control cabinet containing several contactors.

Its bus structure, short-circuit performance, motor-control units, grounding, wireways, barriers, markings, assembly construction, and installed components must work together as one coordinated system.

What Is a Motor Control Center?

A motor control center is an assembly of one or more interconnected vertical sections that contains a common power bus and multiple control or feeder units.

The individual units may control one motor, several related motor functions, or a nonmotor feeder.

Rockwell Automation describes its low-voltage MCC structure as a system of sections containing wireways, doors, and plug-in or frame-mounted units. Multiple sections can be factory assembled into shipping blocks with continuous horizontal power bus and grounding connections.

A typical MCC can perform several functions:

  1. Receive power from an upstream source.
  2. Distribute power through horizontal and vertical busbars.
  3. Protect individual motor branch circuits.
  4. Start and stop motors.
  5. reverse motor direction where required.
  6. Control motor acceleration or speed.
  7. Protect motors against overload conditions.
  8. Interface with PLCs and process-control systems.
  9. Monitor motor and electrical conditions.
  10. Provide an organized structure for maintenance and future expansion.

An MCC can also include feeder devices for transformers, control panels, lighting panels, heaters, and other auxiliary loads when the certified design permits them. Schneider’s current MCC documentation identifies motor starters, branch feeder devices, and certain distribution equipment as possible MCC unit types.

What Does UL845 Cover?

UL845 is the North American product standard specifically associated with motor control centers.

Its published scope applies to MCCs intended for use in accordance with:

  • NFPA 70, the U.S. National Electrical Code
  • CSA C22.1, the Canadian Electrical Code, Part I
  • The applicable Mexican electrical installation code

The current published scope includes qualifying single-phase, three-phase, 50 Hz, 60 Hz, and DC MCCs rated not more than 1,000 V AC or DC. It also establishes a maximum available short-circuit-current boundary of 200,000 A under the scope conditions.

UL845 addresses areas such as:

  • MCC enclosure and structural construction
  • Main and distribution bus systems
  • Motor-control units
  • Disconnecting means
  • Overcurrent protection
  • Motor controllers
  • Overload protection
  • Internal wiring
  • Grounding and bonding
  • Barriers and access
  • Short-circuit performance
  • Temperature performance
  • Markings
  • Unit and assembly requirements

UL845 should not be interpreted as a certification that applies merely because an enclosure contains UL-listed breakers, contactors, overload relays, or VFDs.

The applicable listing relates to the evaluated MCC design and its permitted units, bus structure, component combinations, construction rules, markings, and manufacturing process. Current manufacturer documentation for certified MCC lines identifies the complete assemblies as listed to UL845 rather than relying solely on the individual component certifications.

UL845 and NEMA MCC Requirements

UL845 is commonly used alongside applicable NEMA motor-control standards and installation guidance.

Current North American MCC specifications frequently reference:

  • UL845 for the MCC product-safety requirements
  • NEMA ICS 18 for motor control centers
  • NFPA 70 for installation requirements
  • Applicable CSA requirements for Canadian projects
  • Project-specific utility, owner, and authority requirements

Rockwell’s current MCC specification documentation references both UL845 and NEMA ICS 18 as applicable standards for North American motor control center construction.

These standards do not eliminate the need for project-specific engineering.

The project must still define:

  • System voltage
  • Main bus rating
  • Available fault current
  • Motor ratings
  • Starting methods
  • Control voltage
  • Enclosure type
  • Communication architecture
  • Unit construction
  • Cable routing
  • Environmental conditions
  • Installation location

Main Function of a UL845 MCC

The primary purpose of an MCC is to provide centralized control and protection for multiple motors and related electrical loads.

A typical system arrangement may be:

Utility or transformer → UL891 switchboard or UL1558 switchgear → UL845 MCC → motors, pumps, fans, conveyors, and process equipment

In this arrangement:

  • The switchboard or switchgear provides upstream main and feeder distribution.
  • The MCC receives a feeder and distributes power through its internal bus system.
  • Individual MCC units protect and control each motor.
  • A PLC, distributed control system, or building automation system provides operating commands.
  • Sensors and field devices return process information.

Modern intelligent MCCs can also supply operating data, diagnostics, power information, equipment status, alarms, and predictive-maintenance information to plant systems.

Typical Structure of a UL845 Motor Control Center

A typical low-voltage MCC consists of several interconnected structural and electrical systems.

1. Vertical Sections

The MCC lineup is assembled from one or more floor-standing vertical sections.

Each section may contain:

  • Motor-control units
  • Feeder units
  • VFD units
  • Soft-starter units
  • Main incoming equipment
  • Metering
  • PLC or communication equipment
  • Vertical wireways
  • Horizontal wireways

Sections can be joined to create a lineup sized for the project motor list and future expansion requirements.

Current Rockwell documentation describes MCCs as rigid, free-standing sections that can be assembled into multi-section shipping blocks with continuous bus and grounding systems.

2. Horizontal Main Bus

The horizontal bus distributes incoming power across the MCC lineup.

It connects the incoming section to the vertical distribution bus in each MCC section.

The horizontal bus design must consider:

  • Continuous current
  • Short-circuit rating
  • Bus material
  • Joint design
  • Temperature rise
  • Section connections
  • Shipping splits
  • Future extension
  • Grounding and phase identification

Copper and aluminum bus systems may be available depending on the manufacturer, design, and project specification.

The horizontal bus should not be selected only from the sum of motor nameplate currents. The engineer must also consider demand, diversity, continuous loading, future motors, feeder loads, starting conditions, and the upstream protective device.

3. Vertical Distribution Bus

The vertical bus distributes power from the horizontal main bus to the individual motor-control and feeder units installed within a section.

In plug-in MCC designs, unit power stabs engage with the vertical bus.

The vertical bus system affects:

  • Maximum section loading
  • Unit position
  • Bucket interchangeability
  • Fault-current performance
  • Personnel protection
  • Maintenance access
  • Future unit installation

Some MCC systems include shutters, barriers, or insulated bus options to reduce access to energized parts when a unit is removed. Rockwell identifies structural isolation, automatic shutters, interlocks, continuous bus bracing, and insulated horizontal-bus options among the available safety features of current MCC platforms.

4. Main Incoming Unit

The MCC may receive power through:

  • Main lugs
  • A main circuit breaker
  • A fusible main switch
  • An upstream feeder breaker
  • A transformer connection
  • An adjacent switchboard or switchgear section

The incoming unit may also include:

  • Metering
  • Current transformers
  • Surge protection
  • Ground-fault protection
  • Main bus connections
  • Control power
  • Communication gateways

Whether the MCC needs an internal main protective device depends on the one-line diagram, service arrangement, upstream protection, equipment listing, and project requirements.

5. Motor-Control Units or “Buckets”

The individual modular compartments in an MCC are commonly called buckets, although formal manufacturer documentation may refer to them as units.

A bucket normally contains the components required to control and protect one motor or feeder.

Possible bucket contents include:

  • Disconnecting means
  • Circuit breaker or motor circuit protector
  • Fuses
  • Contactor
  • Overload relay
  • Control transformer
  • Control circuit protection
  • Terminal blocks
  • Auxiliary relays
  • Selector switches
  • Push buttons
  • Pilot lights
  • Communication modules

Current Rockwell MCC systems support modular vertical sections and application-specific MCC buckets, while Schneider documentation describes individual isolated compartments containing combination motor starters and branch feeder devices.

6. Disconnecting Means

Each motor-control unit generally requires a means to disconnect the branch circuit.

Depending on the design, this may be:

  • Molded-case circuit breaker
  • Motor circuit protector
  • Fusible disconnect switch
  • Other approved protective and disconnecting arrangement

The device must be coordinated with:

  • Motor full-load current
  • Motor starting current
  • Branch-circuit conductor protection
  • Contactor rating
  • Overload relay
  • Available fault current
  • Complete unit SCCR

A motor circuit protector and an overload relay perform different functions.

The motor circuit protector addresses short-circuit protection within an approved combination, while the overload relay protects the motor from sustained overcurrent and overload conditions.

7. Contactors and Motor Starters

A contactor electrically opens and closes the motor power circuit in response to a control signal.

When combined with appropriate disconnecting, short-circuit, and overload protection, it becomes part of a motor-starter arrangement.

The contactor may be controlled by:

  • Local start and stop push buttons
  • PLC outputs
  • Pressure switches
  • Float switches
  • Level sensors
  • Temperature controls
  • Building automation systems
  • Process-control systems
  • Remote operator stations

UL508 covers many individual industrial control devices used for starting, stopping, regulating, controlling, or protecting motors, while UL845 applies to the complete MCC in which those components are assembled.

8. Motor Overload Protection

Overload protection helps protect the motor against conditions such as:

  • Mechanical overload
  • Prolonged overcurrent
  • Phase imbalance
  • Phase loss
  • Excessive starting time
  • Locked rotor, depending on the selected device
  • Excessive motor heating

Overload protection may be provided by:

  • Thermal overload relays
  • Electronic overload relays
  • Intelligent motor-protection relays
  • VFD motor-protection functions
  • Soft-starter protection functions

The overload setting should be based on the motor nameplate, applicable code requirements, service factor, temperature conditions, starting characteristics, and manufacturer instructions.

It should not be selected only from the upstream breaker size.

9. Variable Frequency Drive Units

A variable frequency drive controls motor speed and torque by adjusting the frequency and voltage supplied to the motor.

VFD units may be used for:

  • Pumps
  • Fans
  • Conveyors
  • Compressors
  • Mixers
  • Process equipment
  • Energy-saving variable-torque loads

An MCC VFD unit may include:

  • Input disconnect
  • Circuit protection
  • Drive
  • Bypass contactors
  • Line reactor
  • Harmonic-mitigation equipment
  • Output filtering
  • Cooling and ventilation
  • Control and communication devices

VFD units usually require more compartment space and thermal management than conventional starter buckets.

The design must consider drive heat loss, ambient temperature, ventilation, harmonics, cable length, motor insulation, bypass requirements, and maintenance access.

10. Soft-Starter Units

A soft starter reduces the electrical and mechanical stress associated with direct motor starting by controlling the applied voltage during acceleration and, where configured, deceleration.

Soft starters are commonly considered when the project needs:

  • Reduced starting current
  • Reduced mechanical shock
  • Controlled acceleration
  • Controlled pump stopping
  • Less complex speed control than a VFD

Unlike a VFD, a conventional soft starter does not normally provide continuous motor-speed control across the operating range.

The choice between a direct starter, soft starter, and VFD should be based on the load torque, acceleration requirement, speed-control need, energy objective, process operation, motor size, and budget.

11. Feeder Units

An MCC can contain nonmotor feeder units in addition to motor-control units.

These may supply:

  • Local control panels
  • Small transformers
  • Heaters
  • Lighting equipment
  • Auxiliary distribution
  • Process skids
  • Maintenance receptacles
  • Other downstream loads

Schneider’s current MCC documentation identifies branch feeder devices and certain distribution functions as possible units within an MCC structure.

An MCC should not, however, be used as a general substitute for a UL891 switchboard when the project’s primary function is large-scale feeder distribution rather than motor control.

12. Horizontal and Vertical Wireways

Wireways provide organized routes for:

  • Incoming control wiring
  • Outgoing motor cables
  • PLC signals
  • Network cables
  • Instrument wiring
  • Inter-unit wiring
  • Ground conductors

A typical MCC may include:

  • Top horizontal wireway
  • Bottom horizontal wireway
  • Vertical section wireway
  • Rear cable space
  • Dedicated communication routes

Wireway size should be coordinated with the cable schedule rather than selected only from the number of buckets.

Large motors, multiple conductors, shielded VFD cables, separate control wiring, and communication networks can require additional cable space.

13. Grounding and Bonding System

The MCC grounding system may include:

  • Horizontal ground bus
  • Section bonding
  • Unit grounding
  • Door bonding
  • Equipment grounding terminals
  • Shipping-split ground connections

A continuous grounding system is essential across the complete lineup.

Rockwell lists a solid grounding system and continuous grounding connections as fundamental structural features of current UL845 MCC platforms.

The neutral bus, when required for specific loads, is separate from the equipment grounding system and should be designed according to the one-line diagram and system grounding arrangement.

14. Control Power

Motor-control units may use control voltages such as:

  • 120 V AC
  • 24 V DC
  • Other project-specific voltages

Control power may be supplied from:

  • Individual control transformers
  • A common control-power transformer
  • External control power
  • DC power supplies
  • UPS-supported control circuits

The design should define:

  • Control voltage
  • Transformer capacity
  • Primary and secondary protection
  • Grounded or ungrounded control circuit
  • Separate or common control power
  • PLC voltage
  • Solenoid and relay loads
  • Spare control-power capacity

15. Intelligent Monitoring and Communication

An intelligent MCC integrates motor-control devices with digital communication and monitoring systems.

Possible functions include:

  • Motor current monitoring
  • Voltage and power monitoring
  • Overload status
  • Breaker or disconnect status
  • Contactor status
  • Running hours
  • Start count
  • Trip history
  • Fault diagnostics
  • Temperature information
  • Predictive-maintenance alerts
  • Remote control
  • Energy-management data

Eaton describes intelligent MCCs as equipment that combines communications and smart devices to provide actionable data for process, facility, and power-system decisions. Rockwell and Schneider similarly offer intelligent MCC platforms integrating device-level communication, diagnostics, process control, and power monitoring.

Communication options may include project-specific industrial protocols such as Ethernet-based networks, Modbus, PROFIBUS, or other automation systems, depending on the selected equipment.


Fixed, Plug-In, and Removable MCC Units

Not every MCC unit uses the same mounting arrangement.

Fixed Units

A fixed unit is mechanically and electrically installed within the section and normally requires more disassembly for replacement or modification.

Fixed units may be suitable for:

  • Large VFDs
  • Large soft starters
  • Main incoming equipment
  • Special control assemblies
  • Equipment not expected to be frequently replaced

Plug-In or Removable Units

A plug-in unit connects to the vertical bus through power stabs or similar connections.

Depending on the design, it may be removable after the disconnecting means is opened and appropriate safety procedures are followed.

Potential benefits include:

  • Faster unit replacement
  • Standardized spare units
  • Easier future modification
  • Reduced disturbance to main bus connections
  • Modular expansion
  • Improved maintenance organization

Rockwell describes current MCC structures as supporting plug-in and frame-mounted units, while some Schneider systems provide closed-door or remote racking options for engaging or disengaging units from the vertical bus.

Removable construction does not make energized work automatically safe. Maintenance must still follow manufacturer instructions, lockout/tagout requirements, arc-flash precautions, and qualified-person procedures.

Typical UL845 motor control center structure showing incoming, starter, VFD, feeder, PLC, busbar, grounding, and wireway sections.

Common Motor Starting and Control Methods

An MCC may contain several different motor-control methods in one lineup.

Control MethodMain PurposeTypical Use
Direct-on-line starterFull-voltage motor startingSmall or moderate motors where inrush is acceptable
Reversing starterForward and reverse operationConveyors, hoists, positioning equipment
Two-speed starterSelect between defined motor speedsFans, process equipment, special motors
Reduced-voltage starterReduce starting current and torqueLarger motors or constrained power systems
Soft starterControlled acceleration and decelerationPumps, conveyors, compressors
Variable frequency driveContinuous speed and torque controlPumps, fans, conveyors, process loads
Feeder unitSupply a nonmotor downstream loadControl panels, transformers, heaters

The motor-starting method should be selected from the motor and load requirements rather than from enclosure space alone.

Important inputs include:

  • Motor horsepower or kilowatt rating
  • Full-load current
  • Locked-rotor current
  • Load torque
  • Starting frequency
  • Acceleration time
  • Required speed range
  • Process control
  • Mechanical limitations
  • Utility starting-current limits
  • Harmonic requirements
Typical MCC bucket showing power stabs, motor circuit protection, contactor, overload relay, transformer, terminals, controls, and grounding.

Typical UL845 MCC Applications

Motor control centers are widely used where facilities contain multiple motors or repeated motor-control functions.

Common applications include:

  • Water and wastewater treatment
  • Pump stations
  • Manufacturing plants
  • Automotive production
  • Food and beverage processing
  • Mining
  • Metals processing
  • Oil and gas
  • Chemical plants
  • HVAC and cooling systems
  • Conveying and material handling
  • Warehouses and logistics facilities
  • Pulp and paper
  • Textile production
  • Infrastructure projects

Schneider identifies water and wastewater, oil and gas, automotive manufacturing, food and beverage, textiles, chemicals, and steel among common MCC application sectors. Rockwell positions low-voltage MCCs for demanding industrial and infrastructure applications that require modular motor control, diagnostics, and expandability.

Example: Water Treatment Plant

A water treatment MCC may control:

  • Raw-water pumps
  • Transfer pumps
  • Booster pumps
  • Chemical dosing pumps
  • Blowers
  • Mixers
  • Sludge pumps
  • Ventilation fans
  • Conveyors

The MCC may receive power from a UL891 switchboard or UL1558 switchgear.

Individual buckets may contain:

  • Direct starters for small pumps
  • Soft starters for larger pumps
  • VFDs for pressure or flow control
  • Intelligent overload relays
  • PLC communication modules
  • Feeder breakers for auxiliary control panels

The plant PLC may issue start and stop commands, while the MCC returns operating, trip, current, speed, and fault information.

Example: Manufacturing Line

A manufacturing-line MCC may control:

  • Conveyors
  • Hydraulic pumps
  • Cooling pumps
  • Exhaust fans
  • Lubrication systems
  • Compressors
  • Mixers
  • Material-handling equipment

The MCC centralizes the power and motor-control hardware, while a separate PLC or process-control system coordinates the production sequence.

This separation allows the MCC to focus on power, protection, starting, and motor-level monitoring while the automation system manages process logic.

What a UL845 MCC Does Not Automatically Cover

A UL845 MCC certification does not automatically certify:

  • The connected motors
  • The complete machine
  • The complete industrial process
  • Field-installed cables
  • Remote sensors
  • External operator stations
  • The building electrical system
  • The upstream switchboard
  • The project’s PLC software
  • The complete installation

Each connected product and installation remains subject to its own applicable requirements.

Similarly, installing UL-listed starters, breakers, VFDs, or overload relays inside a metal cabinet does not by itself establish that the completed cabinet is a UL845-listed MCC.

Engineering Insight

An MCC should be designed from the motor list and process requirements—not by filling an empty cabinet with available starters.

Before layout begins, the engineer should know:

  • How many motors are required?
  • What is each motor’s horsepower or kilowatt rating?
  • What is each motor’s full-load current?
  • Which motors require reversing?
  • Which motors need soft starters?
  • Which motors need VFD control?
  • What starting current is acceptable?
  • What control voltage is required?
  • What available fault current exists?
  • Is intelligent communication required?
  • Are units fixed or removable?
  • What spare positions are required?
  • What cable-entry direction is required?
  • Is the MCC indoor or outdoor?
  • What enclosure rating is required?
  • What certification pathway applies?

Once these inputs are defined, the engineering team can determine:

  • Main bus rating
  • Vertical bus loading
  • Unit size and quantity
  • Section quantity
  • Wireway capacity
  • Short-circuit rating
  • Starter and drive selection
  • Communication architecture
  • Thermal management
  • Expansion provisions
  • Overall MCC dimensions

A motor control center is therefore not merely a collection of motor starters.

It is a coordinated power-distribution, motor-protection, automation-interface, and maintenance system designed around the operating needs of the complete facility.

UL845 MCC vs Control Panel, Switchboard, Switchgear, and IEC Assembly

Motor control centers are frequently confused with other low-voltage electrical assemblies.

A large industrial facility may contain all of the following equipment:

  • UL845 motor control centers
  • UL508A industrial control panels
  • UL891 switchboards
  • UL1558 low-voltage switchgear
  • IEC 61439 power switchgear and controlgear assemblies
  • Standalone VFD or soft-starter panels
  • PLC and automation cabinets

These assemblies may have similar floor-standing metal enclosures, breakers, busbars, control devices, communication modules, and cable compartments.

However, they do not perform the same primary function and are not evaluated under the same product standards.

The key engineering principle is:

Equipment classification should be based on its primary function, internal power architecture, control-unit construction, protective-device arrangement, applicable standard, and complete certification—not on cabinet size or appearance.

Comparison of UL845 MCC, UL508A control panel, UL891 switchboard, and UL1558 switchgear by function, contents, loads, and system position.

UL845 MCC vs UL508A Industrial Control Panel

A UL845 motor control center and a UL508A industrial control panel can both control motors.

The difference is how the equipment is structured and what role it performs in the facility.

A UL845 MCC is normally a modular, floor-standing assembly with a common horizontal power bus, section distribution buses, wireways, grounding systems, and multiple motor-control or feeder units.

A UL508A industrial control panel is typically a single enclosure or coordinated group of enclosures containing industrial control components used to operate a machine or process.

UL508A covers industrial control panels for general industrial use at 1,000 V or less. UL845 separately covers motor control centers used under the applicable North American installation codes.

Simple Difference

A UL508A control panel manages machine or process logic. A UL845 MCC centralizes the power distribution, protection, starting, and control of multiple motors.

Comparison FactorUL845 Motor Control CenterUL508A Industrial Control Panel
Primary functionCentralized control and protection of multiple motorsControl of a machine, process, or equipment system
Typical constructionMulti-section modular lineupSingle enclosure or coordinated enclosure system
Power architectureCommon horizontal and vertical bus systemCommonly terminal-, breaker-, or distribution-block-based
Functional unitsRepeated motor-control buckets or feeder unitsPLC, relay, contactor, VFD, terminal, and control circuits
Typical downstream loadsMotors, pumps, fans, compressors, conveyorsMachines, valves, actuators, heaters, pumps, sensors
Expansion methodAdditional buckets, unit spaces, or vertical sectionsCabinet modification or additional enclosure
Main standardUL845UL508A

Can a UL508A Panel Control Multiple Motors?

Yes.

A UL508A industrial control panel may contain:

  • Multiple contactors
  • Motor starters
  • Overload relays
  • VFDs
  • Soft starters
  • Motor branch-circuit protection
  • PLCs
  • Safety relays
  • Process-control devices

The number of motors alone does not determine whether the equipment is an MCC.

A multi-motor UL508A control panel may still lack:

  • A continuous MCC main bus
  • Plug-in section distribution buses
  • Standardized removable units
  • Dedicated horizontal and vertical wireways
  • Repeated bucket construction
  • An evaluated UL845 MCC system architecture

UL describes industrial control panels as assemblies of power-circuit and control-circuit components used to control industrial equipment. The UL508A Panel Shop Program applies certification controls to the completed industrial control panel, rather than treating the individual listed components as certification of the full panel.

Can an MCC Include PLC and Automation Equipment?

Yes.

An MCC may contain:

  • PLC sections
  • Remote I/O
  • Communication gateways
  • Control power supplies
  • Network switches
  • Metering equipment
  • Intelligent overload relays
  • Operator interfaces

Adding automation equipment does not automatically turn the complete MCC into a UL508A industrial control panel.

The primary product identity remains dependent on the assembly’s function, construction, certification, and applicable product category.

Example: Pumping System

A pump station may use both products:

UL845 MCC

  • Distributes power to multiple pumps
  • Contains starters or VFD units
  • Provides motor overload protection
  • Includes disconnecting and branch protection
  • Returns motor status and fault information

UL508A Control Panel

  • Reads tank-level and pressure sensors
  • Executes duty and standby logic
  • Controls pump sequencing
  • Generates alarms
  • Communicates with SCADA
  • Sends start and stop commands to the MCC

The MCC handles motor-level power and protection.

The control panel handles process-level operating logic.

UL845 MCC vs UL891 Switchboard

A UL845 motor control center and a UL891 switchboard both receive and distribute electrical power.

Their primary purposes are different.

A UL891 switchboard mainly distributes power through main and feeder protective devices.

A UL845 MCC distributes and controls power specifically for multiple motors and related industrial loads.

UL Solutions identifies UL891 as the principal North American standard for dead-front switchboards, while UL845 is the dedicated standard for motor control centers.

Simple Difference

A switchboard distributes power to many types of downstream equipment. An MCC distributes, protects, and controls power primarily for motors.

Comparison FactorUL845 MCCUL891 Switchboard
Primary functionMotor control and motor feeder distributionMain and feeder power distribution
Common devicesStarters, contactors, overload relays, VFDs, soft startersMain breakers, feeder breakers, fusible switches, metering
Typical loadsMotors, pumps, fans, conveyors, compressorsMCCs, panelboards, transformers, control panels, large loads
Internal structureMotor-control units or bucketsMain and feeder distribution sections
Control capabilityMotor starting, stopping, speed control, monitoringPrimarily distribution-related control and monitoring
Typical system positionDownstream of main distributionMain or upstream distribution
Main standardUL845UL891

A common system arrangement is:

Transformer → UL891 switchboard → UL845 MCC → motors

The switchboard supplies the MCC feeder.

The MCC divides that incoming feeder among individual motor circuits and manages motor operation.


Can an MCC Contain Feeder Breakers?

Yes.

An MCC can contain nonmotor feeder units for loads such as:

  • Control panels
  • Transformers
  • Heaters
  • Auxiliary panels
  • Process skids
  • Local distribution equipment

Schneider Electric’s Model 6 documentation identifies combination motor starters, branch feeder devices, and certain distribution units as possible MCC functional units.

However, an MCC should not automatically replace a switchboard when the project is primarily concerned with large-scale general power distribution.

A switchboard may be more suitable when most outgoing circuits feed:

  • Panelboards
  • Transformers
  • Building feeders
  • Large HVAC distribution panels
  • Other switchboards
  • Mixed nonmotor loads

An MCC is more suitable when a large proportion of outgoing circuits require:

  • Motor starters
  • Overload protection
  • Motor control
  • VFDs
  • Soft starters
  • Motor monitoring
  • Modular motor units

When Both Functions Are Combined

Some industrial lineups may contain adjacent distribution and motor-control sections.

For example:

  • Main incoming section
  • Metering section
  • General feeder section
  • MCC starter section
  • VFD section
  • PLC or communication section

Even when these sections share a coordinated lineup, each portion must follow the applicable product requirements and the complete certified construction.

Similar-looking or physically connected sections should not automatically be assumed to have the same standard classification.

This technical diagram explains the typical structure of a UL67 panelboard used for North American branch circuit distribution. It highlights the main breaker, busbar system, branch circuit breakers, neutral bar, grounding bar, enclosure, dead front cover, circuit directory, and labeling area.

UL845 MCC vs UL1558 Switchgear

UL845 MCCs and UL1558 low-voltage switchgear are both used in industrial facilities, but they operate at different levels of the electrical system.

A UL1558 switchgear assembly primarily provides major low-voltage distribution and protection using low-voltage power circuit breakers.

A UL845 MCC primarily controls and protects multiple motors through motor starters, overload relays, VFDs, soft starters, and feeder units.

UL Solutions lists UL1558 as the standard for metal-enclosed low-voltage power circuit breaker switchgear and UL845 as the separate standard for motor control centers.

Simple Difference

UL1558 switchgear manages major power-system distribution and protection. UL845 MCCs manage motor-level distribution, protection, and operation.

Comparison FactorUL845 MCCUL1558 Switchgear
Primary functionCentralized motor controlMajor low-voltage distribution and protection
Typical circuit devicesMotor starters, motor protectors, feeder breakers, VFDsLow-voltage power circuit breakers
Functional unitsBuckets or motor-control unitsIndividually compartmentalized breaker cells
Typical downstream loadsMotors and motor-driven equipmentMCCs, switchboards, transformers, major feeders
Control focusMotor operation and process interfaceSystem protection, source control, and feeder coordination
Maintenance strategyReplace or service individual motor unitsDrawout power-breaker inspection and replacement
Typical system positionDownstream distributionMain or critical upstream distribution
Main standardUL845UL1558

A typical industrial architecture may be:

Utility → Transformer → UL1558 switchgear → UL845 MCC → motors

In this arrangement:

  • The switchgear provides main and feeder protection.
  • The MCC receives one or more feeder supplies.
  • Individual MCC units control the motors.
  • The process-control system coordinates plant operation.

Why UL1558 Is Not an MCC

UL1558 switchgear may contain:

  • Main breakers
  • Tie breakers
  • Feeder breakers
  • Protective relays
  • Metering
  • Source controls
  • Communication equipment

It normally does not use repeated motor-starter buckets as its primary functional structure.

Similarly, an MCC may contain a main breaker and several large feeder devices, but that does not automatically make it UL1558 switchgear.

The distinction depends on:

  • Breaker category
  • Functional-unit type
  • Primary application
  • Bus and compartment construction
  • Complete assembly standard
  • Certification marking

Can Switchgear Feed Multiple MCCs?

Yes.

A major industrial facility may use one UL1558 lineup to supply:

  • Process MCC 1
  • Process MCC 2
  • Utility MCC
  • HVAC MCC
  • Water-treatment MCC
  • Emergency MCC

This arrangement allows the upstream switchgear to manage the major feeders while each MCC centralizes the motors within a particular process area.

MCC motor-control options including across-the-line, reversing, reduced-voltage, soft starter, VFD, and two-speed starter units.

UL845 MCC vs IEC 61439 Assembly

A North American UL845 MCC is not directly equivalent to an IEC motor control center.

IEC-based MCCs are commonly treated as low-voltage power switchgear and controlgear assemblies under IEC 61439-1 and IEC 61439-2.

IEC 61439-1 establishes general definitions, service conditions, construction requirements, technical characteristics, and verification requirements for low-voltage switchgear and controlgear assemblies. IEC 61439-2 adds the specific requirements for power switchgear and controlgear assemblies rated up to 1,000 V AC or 1,500 V DC.

Simple Difference

UL845 is a North American product standard specifically for motor control centers. IEC 61439 provides an international assembly framework that can include motor-control functional units.

Comparison FactorUL845 MCCIEC 61439 MCC or PSC Assembly
Primary marketUnited States, Canada, Mexico, and North American-standard projectsIEC and international markets
Assembly standardUL845IEC 61439-1 and IEC 61439-2
Typical component standardsUL and CSA component standardsIEC 60947 component standards
Installation frameworkNEC, CEC, Mexican installation rulesNational adoption of IEC requirements and local codes
Assembly approachUL845-evaluated MCC systemIEC design verification and routine verification
Starter terminologyNEMA- or manufacturer-defined units and combinationsIEC utilization categories and coordination types
Enclosure languageNEMA enclosure Type commonly usedIP code and IEC assembly classifications commonly used
Direct equivalenceNoNo

IEC 60947-4-1 applies to electromechanical contactors and motor starters, including motor-protective switching devices, while IEC 60947-2 applies to low-voltage circuit breakers. Semiconductor motor controllers and soft starters are addressed through IEC 60947-4-2.

Why They Are Not Interchangeable

A UL845 MCC and an IEC 61439 MCC may perform similar operating functions, but they can differ in:

  • Component certifications
  • Breaker and starter standards
  • Busbar verification
  • Short-circuit evaluation
  • Temperature-rise verification
  • Electrical clearances
  • Unit construction
  • Internal separation
  • Enclosure classifications
  • Markings
  • Documentation
  • Installation rules
  • Certification and inspection pathways

An IEC 61439-verified MCC should not automatically be advertised as UL845 listed.

Likewise, a UL845 MCC should not automatically be represented as IEC 61439 verified unless the required IEC verification has been completed.

Can One MCC Be Designed for Both Markets?

A dual-market design may be possible, but it must be planned from the beginning.

Engineers should review:

  • UL and IEC component availability
  • North American and IEC breaker standards
  • Motor starter combinations
  • Wire sizes and conductor markings
  • Busbar clearances
  • SCCR and IEC short-circuit ratings
  • Temperature-rise verification
  • Control voltage
  • Terminal standards
  • NEMA Type and IP requirements
  • Product markings
  • Required certification bodies
  • Installation documentation

Trying to convert a completed IEC MCC into a UL845 MCC after manufacturing can require extensive redesign.

NEMA MCC vs IEC MCC

The term NEMA MCC is commonly used for North American MCCs designed around UL845, applicable NEMA practices, and North American motor-control components.

The term IEC MCC commonly refers to an assembly designed under IEC 61439 with devices selected from the IEC 60947 series.

NEMA documentation identifies standards and guidance for North American motor control centers, while major UL845 MCC platforms are marketed as meeting UL845 and applicable NEMA requirements.

Typical Differences

Selection AreaNEMA / UL845 MCCIEC MCC
Main assembly frameworkUL845 and applicable NEMA requirementsIEC 61439-1 and IEC 61439-2
Contactor and starter approachNEMA-sized or North American combinationsIEC-rated components selected by application and utilization category
Circuit breakersUL or CSA-certified productsIEC 60947-2 devices
Motor startersUL component combinationsIEC 60947-4-1 or IEC 60947-4-2 devices
Short-circuit terminologyComplete MCC SCCRRated short-time, peak, and conditional short-circuit values as applicable
Enclosure classificationNEMA TypeIP rating and IEC assembly requirements
VerificationUL product evaluation and production follow-upDesign verification and routine verification
Common unitsInches and AWG, depending on projectMetric dimensions and mm², depending on project

These are typical distinctions rather than absolute rules.

Some North American MCC platforms use IEC-style contactors, while international projects may specify North American brands or operating conventions.

The complete specification and certification pathway remain more important than the component appearance.

NEMA Starter Size vs IEC Contactor Selection

Traditional NEMA motor starters are commonly selected using standardized NEMA sizes.

IEC contactors are typically selected more closely around:

  • Motor current
  • Motor power
  • Utilization category
  • Duty cycle
  • Switching frequency
  • Coordination requirement
  • Operating voltage

Neither approach is automatically better.

A NEMA-sized starter may provide broader application margins and easier standardization.

An IEC-selected starter may provide more compact, application-specific selection.

The engineer should follow the motor data, starting duty, project standard, and manufacturer coordination tables.

Fixed vs Plug-In or Removable MCC Units

MCC functional units may be fixed, plug-in, withdrawable, or otherwise removable depending on the MCC platform.

Rockwell Automation describes current North American MCC units as either removable plug-in units or frame-mounted non-plug-in units. Schneider Electric describes MCC control units mounted in individual isolated compartments.

Fixed Units

A fixed unit is mechanically mounted and connected within the MCC section.

Fixed construction is commonly considered for:

  • Large VFDs
  • Large soft starters
  • Main incoming units
  • Large feeder devices
  • PLC sections
  • Special control assemblies
  • Equipment that is unlikely to be regularly replaced

Advantages of Fixed Units

  • Simple mechanical construction
  • Suitable for large or heavy devices
  • Flexible custom layouts
  • Fewer plug-in power interfaces
  • Potentially lower initial cost

Limitations of Fixed Units

  • More disassembly may be required for replacement
  • Permanent cables or bus connections may need to be disconnected
  • Unit changes may take longer
  • Section shutdown may be required
  • Future replacement may require greater field work

Plug-In or Removable Units

A plug-in unit typically connects to the section distribution bus through power stabs.

The unit can be removed according to the manufacturer’s procedures after the circuit has been isolated and the required safety steps have been completed.

Potential Advantages

  • Faster unit replacement
  • Standardized spare units
  • Easier modification
  • Reduced disturbance to the main bus
  • Modular future expansion
  • Easier workshop repair
  • More organized maintenance

Potential Limitations

  • Higher mechanical complexity
  • Product-specific interchangeability
  • Additional power-stab maintenance
  • Unit-size restrictions
  • Not all devices are suitable for removable construction
  • Greater initial cost in some designs

Removable does not necessarily mean interchangeable.

Two units that occupy the same physical space may differ in:

  • Power-stab rating
  • Short-circuit rating
  • Control connector
  • Starter size
  • Overload setting
  • Wiring
  • Door interlock
  • Communication architecture
  • Certification

The replacement unit must match the approved MCC system and project requirements.

Can a Unit Be Removed While the MCC Is Energized?

The answer depends on the specific MCC design, unit position, manufacturer instructions, electrical condition, and approved safety procedure.

A removable unit should never be assumed safe to remove from an energized bus merely because it is called plug-in or withdrawable.

Personnel must follow:

  • Manufacturer instructions
  • Disconnect and interlock procedures
  • Lockout/tagout
  • Arc-flash requirements
  • Site safety rules
  • Qualified-person procedures

Some current MCC platforms offer closed-door isolation, unit racking, shutters, or remote operating features, but those features are product-specific and must not be assumed for every UL845 MCC.

Standard MCC vs Intelligent MCC

A conventional MCC controls and protects motors through hardwired power and control circuits.

An intelligent MCC adds networked devices, diagnostics, communication, software, and data integration.

Schneider Electric describes its intelligent MCC as using the same overall Model 6 MCC structure with additional hardwired or networked intelligent capabilities. Rockwell’s IntelliCENTER platform combines its MCC structure with EtherNet/IP, intelligent motor-control devices, and monitoring software.

Standard MCC

A standard MCC may use:

  • Hardwired start and stop signals
  • Auxiliary contacts
  • Pilot lights
  • Conventional overload relays
  • Local selector switches
  • Terminal-block connections
  • Basic meters

It may be appropriate when:

  • The process is simple
  • Remote diagnostics are unnecessary
  • The control system already receives hardwired signals
  • Network infrastructure is limited
  • Initial cost is a major priority
  • Maintenance personnel prefer conventional circuits

Intelligent MCC

An intelligent MCC may integrate:

  • Networked overload relays
  • VFD communication
  • Soft-starter communication
  • Breaker or disconnect status
  • Current, voltage, and power data
  • Trip history
  • Start count
  • Running hours
  • Thermal information
  • Predictive-maintenance data
  • Remote configuration
  • Device diagnostics
  • Asset-management software

It may be suitable when the facility prioritizes:

  • Remote monitoring
  • Faster fault diagnosis
  • Reduced control wiring
  • Process data
  • Predictive maintenance
  • Energy management
  • Centralized asset information
  • Integration with PLC, DCS, or SCADA systems

Intelligent Does Not Mean Autonomous

An intelligent MCC does not automatically provide:

  • Safe process logic
  • Functional safety
  • Cybersecurity
  • Automatic fault recovery
  • Predictive maintenance without engineering
  • Remote operation authorization
  • Complete SCADA integration

The communication and control architecture must still define:

  • Command ownership
  • Local and remote control priority
  • Network failure behavior
  • Safe-state response
  • Access control
  • User permissions
  • Network segmentation
  • Backup operation
  • Cybersecurity responsibilities
  • Functional-safety requirements

The intelligence layer supplements the MCC’s electrical protection and control functions; it does not replace them.

Quick Equipment Classification Guide

Main Project RequirementMore Relevant Equipment Category
Control one machine or processUL508A industrial control panel
Control and protect many motors from a centralized lineupUL845 MCC
Main and feeder power distributionUL891 switchboard
Drawout power-breaker distribution for critical systemsUL1558 switchgear
IEC power and motor-control assemblyIEC 61439-1 and IEC 61439-2 assembly
Standalone speed control for one motorVFD panel or industrial control panel
Building branch-circuit distributionUL67 panelboard
Large custom enclosure without evaluated assemblyEnclosure only

This table is an initial classification tool.

The final decision must consider the one-line diagram, motor list, assembly structure, breaker and starter types, certification requirements, and installation market.

Common Equipment-Classification Mistakes

Mistake 1: Calling Every Multi-Motor Panel an MCC

A control panel containing several starters is not automatically a UL845 MCC.

The equipment may instead be:

  • A UL508A multi-motor control panel
  • A machine control panel
  • A VFD panel
  • A pump control panel
  • An unlisted custom assembly

A true MCC normally includes a coordinated section, bus, unit, grounding, wireway, and certification architecture.


Mistake 2: Calling an MCC a Switchboard Because It Has a Main Breaker

A main breaker does not define the complete equipment category.

An MCC may include a main breaker but remain an MCC because its primary downstream functions are motor-control units.

A switchboard may feed motors but remain a switchboard when its primary function is general feeder distribution.


Mistake 3: Calling an MCC Switchgear Because It Has Separate Compartments

Compartmentalization alone does not make equipment UL1558 switchgear.

MCCs also use isolated motor-control compartments.

UL1558 classification depends on the complete metal-enclosed power circuit breaker switchgear construction, not merely the presence of compartment doors.


Mistake 4: Treating IEC 61439 and UL845 as Equivalent

Both may be used for motor-control assemblies, but their component systems, verification methods, markings, and market-access pathways differ.

Compliance with one standard does not automatically establish compliance with the other.


Mistake 5: Assuming Listed Components Create a Listed MCC

UL-listed breakers, starters, overload relays, drives, and terminals do not independently certify the finished MCC.

The complete assembly must follow the applicable UL845 construction, ratings, component combinations, markings, and manufacturing requirements. UL845 applies to the motor control center as a product category, while individual motor-control devices may be evaluated under separate component standards such as UL508.


Mistake 6: Assuming Plug-In Units Can Always Be Removed Live

Plug-in describes the connection method.

It does not automatically authorize energized removal.

The specific MCC construction, unit position, isolation mechanism, manufacturer instructions, and electrical-safety procedure must be followed.


Mistake 7: Assuming an Intelligent MCC Replaces the PLC

An intelligent MCC provides motor-level data, control interfaces, diagnostics, and communication.

The PLC or process-control system normally remains responsible for:

  • Operating sequence
  • Interlocks
  • Process logic
  • Production coordination
  • Alarm strategy
  • System-level decisions

The two systems work together rather than replace one another.


Mistake 8: Using a Component SCCR as the Complete MCC Rating

The short-circuit rating of one breaker, starter, or overload relay is not automatically the rating of the complete MCC.

The complete rating depends on the approved combination of:

  • Disconnecting means
  • Overcurrent protective device
  • Motor controller
  • Overload protection
  • Bus structure
  • Unit construction
  • Assembly configuration

UL’s combination motor-controller resources distinguish between the ratings of individual components and the ratings established for the approved component combination.

Engineering Insight

The correct equipment category should be determined before detailed cabinet design begins.

Ask these questions first:

  • Is the equipment primarily distributing power or controlling motors?
  • Does it require a common MCC bus system?
  • Are repeated motor-control units required?
  • Is a PLC process-control enclosure also needed?
  • Are the motors controlled through starters, soft starters, or VFDs?
  • Are units fixed or removable?
  • Does the project require intelligent communication?
  • Is the project North American or IEC-based?
  • What complete assembly certification is required?
  • What available fault current exists?
  • How will the equipment be maintained and expanded?

Once these questions are answered, the project can be correctly classified as:

  • UL845 MCC
  • UL508A industrial control panel
  • UL891 switchboard
  • UL1558 switchgear
  • IEC 61439 assembly
  • Standalone starter or drive panel
  • Enclosure-only solution

Correct classification at the beginning reduces redesign, certification risk, component mismatch, installation problems, and project delays.

How to Specify and Select a UL845 Motor Control Center

A UL845 motor control center should be designed from the electrical system, motor list, process requirements, and maintenance strategy.

The cabinet dimensions and bucket arrangement should be the result of engineering decisions—not the starting point.

UL845 is currently an active standard for MCCs rated up to 1,000 V AC or DC and used on circuits with available short-circuit current not exceeding 200,000 A under the standard’s scope. The active sixth edition was last revised in February 2025. However, these scope limits are not automatic ratings for every MCC. The actual voltage, current, and SCCR must be confirmed for the specific evaluated construction.

Before requesting a quotation, the buyer should provide:

  • One-line diagram
  • Complete motor list
  • System voltage and grounding arrangement
  • Main bus and incoming-device requirements
  • Available fault current
  • Motor starting and speed-control methods
  • Unit construction requirements
  • Control voltage
  • PLC and communication architecture
  • Cable-entry information
  • Installation environment
  • Maintenance and expansion strategy
  • Required certification and documentation

Current manufacturer selection procedures similarly begin with certification, network technology, structure, bus systems, unit design, and unit type rather than only enclosure dimensions.


Step 1: Define the MCC’s Position in the Electrical System

First determine where the MCC is located in the one-line diagram.

The MCC may receive power from:

  • A UL891 switchboard
  • UL1558 low-voltage switchgear
  • A transformer
  • An automatic transfer switch
  • A generator distribution system
  • Another upstream MCC
  • An IEC or project-specific distribution assembly

It may supply:

  • Pumps
  • Fans
  • Compressors
  • Conveyors
  • Mixers
  • Blowers
  • Crushers
  • Cooling towers
  • Hydraulic systems
  • Process skids
  • Auxiliary control panels
  • Small transformers or nonmotor feeders

A typical architecture is:

Utility or transformer → Main switchboard or switchgear → UL845 MCC → Motor-control units → Motors

The one-line diagram should identify:

  • Incoming source
  • Upstream protective device
  • Main MCC device
  • Main bus rating
  • Grounding system
  • Motor feeders
  • Nonmotor feeders
  • Alternate sources
  • Tie or transfer arrangements
  • Downstream control systems

The system position affects the incoming section, main-device selection, neutral and grounding arrangement, SCCR, metering, cable entry, and service-equipment requirements.


Step 2: Prepare a Complete Motor List

The motor list is the most important MCC design input.

Each motor should be listed separately rather than grouped only by total horsepower.

A useful motor schedule should include:

Required InformationExample
Equipment tagP-101A
Load descriptionRaw-water pump
Motor powerProject-specific HP or kW
Full-load currentFrom motor nameplate or engineering data
Voltage and phaseFor example, three-phase system
Starting methodAcross-the-line, reversing, soft starter, or VFD
DutyContinuous, intermittent, or standby
Service factorMotor-specific
Control locationLocal, remote, PLC, or SCADA
Feedback signalsRun, trip, available, speed, current
Cable informationSize, quantity, shielding, and length
Spare requirementInstalled spare, empty space, or future unit

The motor list should also identify:

  • Motor efficiency class
  • Locked-rotor or starting-current information
  • Number of starts per hour
  • Acceleration time
  • Required speed range
  • Load torque characteristics
  • Reversing requirement
  • Emergency-stop requirement
  • Brake or heater circuits
  • Motor temperature sensors
  • Space-heater requirement
  • Hazardous-area requirements
  • Bypass requirement for VFD or soft starter

A motor’s horsepower alone is not enough to select the starter, overload relay, breaker, conductor, unit size, or control strategy.


Step 3: Confirm Voltage, Phase, Frequency, and Grounding

The buyer should provide a complete electrical system description.

Required information includes:

  • Nominal voltage
  • Single-phase or three-phase
  • Frequency
  • Three-wire or four-wire system
  • Grounded or ungrounded system
  • Neutral requirement
  • Control voltage
  • Auxiliary voltage
  • External or internal control-power source

UL845 covers qualifying single-phase, three-phase, 50 Hz, 60 Hz, and DC MCCs within its published scope, but the available configurations depend on the evaluated MCC platform.

The grounding arrangement may affect:

  • Ground-fault protection
  • Breaker configuration
  • Metering
  • Control transformers
  • Surge protection
  • Neutral-bus requirements
  • VFD filters
  • Fault detection
  • Equipment markings

Do not specify only “480V MCC.”

A more complete description would define the voltage, phase, wire system, frequency, grounding arrangement, and control voltage.


Step 4: Determine the Main Bus Rating

The horizontal main bus must support the calculated MCC load and planned future expansion.

The bus rating should consider:

  • Motor full-load currents
  • Demand and diversity
  • Continuous loads
  • Nonmotor feeder loads
  • Simultaneously operating motors
  • Largest motor starting condition
  • VFD and soft-starter loads
  • Future motors
  • Spare units
  • Main protective-device rating
  • Upstream transformer capacity

Do not simply add every motor’s nameplate current and select the next bus rating.

Some motors may not operate simultaneously, while other continuous or future loads may require additional capacity.

Manufacturer MCC platforms offer project-specific bus materials, ratings, plating, ground-bus options, and section configurations. For example, Rockwell’s current selection guide treats electrical system, incoming power, horizontal and vertical bus capacity, bus withstand, ground bus, and SCCR as a dedicated selection stage.

The specification should identify:

  • Horizontal bus ampere rating
  • Copper or aluminum bus
  • Bus plating, where required
  • Neutral bus, if required
  • Ground bus
  • Vertical bus rating
  • Future bus extension
  • Bus splice requirements
  • Short-circuit bracing
  • Shipping-split arrangement

Step 5: Select the Incoming Configuration

The MCC may use:

Main Lugs Only

A main-lug-only MCC depends on an upstream protective device.

This may be suitable when:

  • The MCC is supplied from a nearby switchboard or switchgear feeder
  • The upstream breaker provides required protection
  • A separate disconnect is available
  • The one-line diagram specifically calls for main lugs only

Main Circuit Breaker

A main breaker may provide:

  • Local isolation
  • MCC overcurrent protection
  • Ground-fault protection
  • Shunt trip
  • Undervoltage release
  • Communication
  • Main metering integration

The specification should identify:

  • Frame and trip rating
  • Number of poles
  • Interrupting rating
  • Trip-unit functions
  • Ground-fault requirement
  • Remote trip or close functions
  • Auxiliary contacts
  • Fixed or removable construction

Fusible Main Disconnect

A fusible main arrangement may be selected where:

  • Current-limiting fuse performance is required
  • The plant standard favors fusible protection
  • Selective-coordination or SCCR strategies use specific fuse classes
  • Customer maintenance practices support fuse replacement

Multiple Incoming Sources

A more complex MCC may be supplied by:

  • Two transformers
  • Utility and generator
  • Main-tie-main arrangement
  • Normal and emergency sources
  • Transfer equipment
  • Redundant industrial power systems

The project must define the operating sequence, permitted source combinations, interlocking, transfer method, load shedding, and whether parallel operation is permitted.


Step 6: Confirm Available Fault Current and MCC SCCR

The available fault current at the MCC installation point must be provided before final unit and bus selection.

The project engineer should identify:

  • Available RMS symmetrical fault current
  • System voltage
  • Utility contribution
  • Transformer impedance
  • Generator contribution
  • Motor contribution
  • Parallel-source operating conditions
  • Future transformer or generator additions
  • Required complete-MCC SCCR

UL845 includes requirements for short-circuit performance of the MCC and its units. The standard’s current published scope permits MCCs on circuits up to 200,000 A available short-circuit current, but the actual marked rating of a particular lineup may be much lower and configuration-dependent.

The complete MCC SCCR should not be inferred from only:

  • The main breaker interrupting rating
  • One motor circuit protector
  • One contactor
  • One VFD
  • One overload relay
  • The horizontal bus rating

The approved motor-controller combination may include a disconnect, overcurrent protective device, motor controller, and overload protection. UL’s SCCR guidance emphasizes that the higher combination rating applies only when all specified components are used and installed under the stated conditions.

SCCR requirements can affect:

  • Breaker or fuse selection
  • Starter combination
  • VFD input protection
  • Bus bracing
  • Unit construction
  • Component spacing
  • Section configuration
  • Certification scope
  • Equipment cost

The fault-current information should therefore be supplied at the RFQ stage rather than after the MCC layout has been approved.


Step 7: Select the Motor Starting Method

Each motor should be assigned the correct starting and control method.

Across-the-Line Starter

An across-the-line starter applies full system voltage to the motor.

It is commonly suitable when:

  • Starting current is acceptable
  • The power system can support the inrush
  • Full starting torque is needed
  • Speed control is unnecessary
  • The mechanical load can tolerate direct starting

Reversing Starter

A reversing starter is used when the motor must operate in both directions.

Applications may include:

  • Conveyors
  • Hoists
  • Positioning systems
  • Gates
  • Material-handling equipment

Electrical and mechanical interlocking must prevent simultaneous forward and reverse contactor operation.

Two-Speed Starter

A two-speed starter may be used with motors designed for two defined operating speeds.

The motor winding arrangement and required connection must be clearly specified.

Reduced-Voltage Starter

Reduced-voltage starting may be considered where full-voltage starting creates excessive:

  • Utility voltage drop
  • Transformer loading
  • Mechanical stress
  • Starting current
  • Process disturbance

Soft Starter

A soft starter is commonly used when controlled acceleration or deceleration is required without continuous speed regulation.

Applications may include:

  • Pumps
  • Conveyors
  • Compressors
  • Fans
  • Mechanical systems sensitive to shock

Variable Frequency Drive

A VFD is appropriate when the project requires:

  • Continuous speed control
  • Process-flow control
  • Pressure regulation
  • Energy reduction on variable-torque loads
  • Controlled acceleration
  • Torque management
  • Communication and diagnostics

Current UL845 MCC platforms can integrate across-the-line starters, electronic overload relays, soft starters, and variable-speed drives within one coordinated lineup.

The starting method should be based on motor and process performance—not only the smallest available bucket size.


Step 8: Select the Motor Branch-Circuit Combination

A complete motor branch circuit commonly includes several separate functions:

  1. Disconnecting means
  2. Short-circuit and ground-fault protection
  3. Motor controller
  4. Motor overload protection

The selected combination must match the motor rating, voltage, SCCR, starting method, and evaluated component combination.

UL identifies multiple combination motor-controller constructions involving specific disconnects, fuses or breakers, motor controllers, and overload protection. The combination rating applies only when the listed components and stated conditions are followed.

The specification should define:

  • Breaker, motor circuit protector, or fused disconnect
  • Contactor or solid-state controller
  • Overload-relay type
  • Motor horsepower and current
  • Required SCCR
  • Trip class
  • Phase-loss protection
  • Ground-fault monitoring
  • Communication requirement
  • Manual or automatic reset
  • Local isolation requirement

Overload Relay Selection

An overload relay may provide:

  • Thermal overload protection
  • Electronic overload protection
  • Phase-loss detection
  • Phase-imbalance detection
  • Jam protection
  • Stall protection
  • Ground-fault monitoring
  • Motor thermal model
  • Trip history and diagnostics

The overload setting should be based on motor data and applicable engineering requirements, not the upstream breaker rating.


Step 9: Choose Fixed, Plug-In, or Removable Units

The unit construction affects maintenance, spare strategy, expansion, and cost.

Fixed Units

Fixed units are often suitable for:

  • Large VFDs
  • Large soft starters
  • Main breakers
  • High-current feeders
  • PLC sections
  • Special control assemblies

They may offer greater layout flexibility for large equipment, but replacement can require additional disassembly and shutdown time.

Plug-In or Removable Units

Plug-in units may support:

  • Faster replacement
  • Standardized spare buckets
  • Easier workshop repair
  • Future modification
  • Reduced disturbance to permanent bus connections
  • Modular expansion

Current MCC platforms may offer plug-in replacement units, automatic shutters, interlocks, and product-specific closed-door isolation technologies. These features are manufacturer- and configuration-dependent and must not be assumed for every UL845 MCC.

The buyer should clarify whether “removable” means:

  • Removable after the lineup is de-energized
  • Isolatable with the door closed
  • Withdrawable to a disconnected position
  • Replaceable without disconnecting field wiring
  • Equipped with separable control connectors
  • Designed for remote racking

Plug-in construction does not automatically authorize energized unit removal.

Manufacturer instructions, lockout/tagout procedures, arc-flash requirements, and qualified-person rules still apply.


Step 10: Determine Unit Sizes and Section Arrangement

The number and type of units determine the quantity and width of vertical sections.

The engineering team should allocate space for:

  • Main incoming unit
  • Across-the-line starter buckets
  • Reversing starter buckets
  • Soft starters
  • VFDs
  • Feeder breakers
  • Control transformers
  • PLC or remote-I/O sections
  • Network switches
  • Metering
  • Spare units
  • Future spaces
  • Horizontal and vertical wireways

A small starter may occupy only part of a section, while a large VFD or feeder may require a complete section or frame-mounted construction.

Current MCC selection guides treat section structure, depth, wireways, unit design, and unit type as separate configuration stages. Available section dimensions and unit-space arrangements vary by manufacturer and equipment size.

The lineup drawing should show:

  • Section numbers
  • Unit tags
  • Unit heights
  • Incoming section
  • Bus location
  • Wireways
  • Spare spaces
  • VFD ventilation
  • Shipping splits
  • Cable-entry direction
  • Overall dimensions

Step 11: Plan VFD and Soft-Starter Thermal Management

VFDs and soft starters can generate more heat than conventional electromechanical starter units.

The MCC design may require:

  • Larger compartments
  • Ventilated doors
  • Forced ventilation
  • Cooling fans
  • Heat-exchanger or air-conditioning discussion
  • Component derating
  • Wider or deeper sections
  • Temperature sensors
  • Separation from heat-sensitive control equipment

The specification should identify:

  • Ambient temperature
  • Installation altitude
  • Motor current
  • Drive duty
  • Switching frequency
  • Carrier-frequency requirements
  • Bypass configuration
  • Harmonic limits
  • Line-reactor requirements
  • Output-filter requirements
  • Motor cable length
  • Regenerative operation
  • Braking-resistor requirements

Current manufacturer documentation applies defined ambient and altitude limits and may require different derating rules for MCCs containing VFDs. These limits are product-specific and must be verified for the selected drive and MCC platform.

Harmonic Considerations

A project containing many drives may require review of:

  • Total harmonic distortion
  • Transformer loading
  • Generator compatibility
  • Power-factor correction
  • Line reactors
  • Passive filters
  • Active harmonic filters
  • Multi-pulse or active-front-end drives

Harmonic mitigation should be based on the system study rather than automatically adding the same accessory to every drive.


Step 12: Define the Control Architecture

The MCC specification should explain how each motor is controlled.

Possible control modes include:

  • Local manual control
  • Remote hardwired control
  • PLC control
  • DCS control
  • SCADA command
  • Building automation control
  • Automatic sensor-based operation
  • Local/remote selector control

For each motor, define:

  • Start command
  • Stop command
  • Emergency stop
  • Permissive signals
  • Interlocks
  • Run feedback
  • Trip feedback
  • Available status
  • Local/remote status
  • Speed reference
  • Motor current
  • Fault reset
  • Bypass operation

The control philosophy should state which system owns the final command.

For example:

  • PLC controls process sequence.
  • MCC provides motor protection and starter operation.
  • Local selector permits maintenance control.
  • Emergency stop overrides normal commands.
  • Communication failure causes a defined safe response.

Unclear command ownership can create unsafe or unpredictable equipment operation.


Step 13: Select the Control Voltage

The specification should identify the required control voltage, such as:

  • 120V AC
  • 24V DC
  • Another project-specific voltage

Control power may be provided by:

  • Individual unit control transformers
  • Common MCC control transformer
  • External control-power source
  • DC power supplies
  • UPS-supported source

The designer should calculate:

  • Contactor coil loads
  • Relay loads
  • Pilot lights
  • Solenoid loads
  • PLC and remote-I/O loads
  • Communication equipment
  • Spare capacity
  • Transformer inrush
  • Secondary protection

Eaton notes that a motor starter unit commonly uses a lower-voltage control circuit to operate a higher-voltage power circuit, with push buttons, selector switches, and status indication forming part of the control arrangement.


Step 14: Define Intelligent MCC and Communication Requirements

An intelligent MCC can integrate networked overload relays, drives, soft starters, meters, PLCs, and communication gateways.

Possible data points include:

  • Motor current
  • Voltage
  • Power
  • Energy
  • Run status
  • Trip status
  • Overload condition
  • Start count
  • Running hours
  • Thermal capacity
  • Fault history
  • Drive speed
  • Process data
  • Maintenance warnings

Current intelligent MCC platforms support major industrial networks and can be factory configured with device addresses, motor information, protection settings, and functional tests.

The buyer should define:

  • Communication protocol
  • Network topology
  • Ethernet-switch location
  • Fiber or copper network
  • Device IP-address strategy
  • Redundant network requirement
  • PLC or DCS interface
  • SCADA tags
  • Time synchronization
  • Remote-access policy
  • Cybersecurity responsibility
  • Factory configuration
  • Site commissioning scope

Common industrial protocols may include EtherNet/IP, Modbus TCP or RTU, PROFIBUS, or PROFINET, depending on the selected platform.

Communication Failure Behavior

The specification should state what happens when communication is lost.

Possible responses include:

  • Motor continues its last valid command
  • Motor stops
  • Local hardwired control remains available
  • PLC alarm is generated
  • Automatic restart is prohibited
  • Essential motors use redundant hardwired signals

Network communication should not replace required hardwired safety functions unless the complete functional-safety architecture has been properly designed and evaluated.


Step 15: Plan Wireways, Cable Entry, and Terminations

An MCC may require substantial space for motor, control, instrumentation, and communication cables.

Provide:

  • Motor cable size
  • Number of conductors
  • Shielding requirement
  • Ground conductor size
  • Top or bottom entry
  • Front or rear termination
  • Conduit quantity and size
  • Cable-tray location
  • VFD cable type
  • Control cable quantity
  • Network cable routing
  • Instrument cable separation
  • Spare cable requirements

Current MCC structures may use continuous top and bottom horizontal wireways together with dedicated vertical wireways isolated from the power bus. Wider wireway options may be required for larger cable quantities.

The cable design should consider:

  • Bending space
  • Lug capacity
  • Multiple conductors per phase
  • Cable support
  • Shield termination
  • Separation of power and communication wiring
  • VFD output-cable routing
  • Electromagnetic interference
  • Field installation access

A lineup with enough unit space may still be unsuitable if its wireways cannot accommodate the actual field cabling.


Step 16: Select the Enclosure and Installation Environment

The installation environment affects enclosure type, ventilation, material, coating, heaters, and corrosion protection.

The project should identify:

  • Indoor or outdoor location
  • Dust level
  • Moisture exposure
  • Dripping liquid
  • Direct rain
  • Humidity
  • Condensation
  • Ambient temperature
  • Altitude
  • Coastal salt exposure
  • Chemical exposure
  • Wastewater gases
  • Washdown requirements
  • Hazardous area classification

Manufacturer MCC platforms may offer different NEMA/UL enclosure constructions, such as general-purpose, dust-resistant, outdoor, or stainless-steel options, but available Types and equipment combinations depend on the evaluated platform.

Outdoor MCC Considerations

An outdoor MCC may require:

  • Weather-resistant roof
  • Drip protection
  • Space heaters
  • Thermostats or humidistats
  • Sealed cable entry
  • Corrosion-resistant coating
  • UV-resistant exterior finish
  • Stainless steel construction
  • Ventilation rain hoods
  • Condensation drainage
  • Walk-in or non-walk-in outer enclosure

An indoor MCC installed inside a separately fabricated outdoor shell should not automatically be represented as an outdoor UL845-listed assembly. The complete construction and environmental rating must be included in the applicable certification pathway.


Step 17: Address Arc-Flash Risk

UL845 certification does not automatically mean the MCC is arc-resistant.

Arc-flash risk should be addressed through the complete electrical-safety strategy.

Possible measures include:

  • Current-limiting protection
  • Faster breaker clearing
  • Energy-reducing maintenance mode
  • Zone-selective interlocking
  • Remote monitoring
  • Remote operation
  • Closed-door isolation
  • Infrared inspection windows
  • Automatic bus shutters
  • Arc detection
  • Arc-resistant MCC construction

Current product platforms offer separately engineered arc-resistant MCC options tested to defined IEEE C37.20.7 arrangements. The protection depends on the tested configuration, secured doors, specified bus rating, enclosure type, pressure-relief arrangement, and installation instructions.

The specification must distinguish between:

  • Arc-flash mitigation features
  • Arc-energy reduction
  • Remote operation
  • Arc detection
  • Arc-resistant construction

These are not interchangeable terms.


Step 18: Plan Maintenance and Spare Units

The maintenance strategy should be defined before production.

Questions include:

  • Will the MCC be periodically de-energized?
  • Are plug-in spare buckets required?
  • Will spare contactors and overload relays be stored?
  • Are complete spare VFDs required?
  • Can a motor tolerate extended downtime?
  • Who is authorized to modify the MCC?
  • Are infrared inspection points required?
  • Is condition monitoring required?
  • Must units be repaired off-site?
  • Are obsolete-device replacement plans needed?

Current MCC systems may use plug-in replacement units, intelligent diagnostics, interlocks, through-door communication access, and viewing windows to support maintenance and reduce exposure.

The spare-unit specification should identify:

  • Unit size
  • Starter size
  • Breaker or fuse configuration
  • Overload range
  • Control voltage
  • Control connector
  • Door operator
  • Network module
  • SCCR
  • Motor rating
  • Required factory configuration

A spare bucket is useful only when it matches the approved MCC system and intended motor circuit.


Step 19: Define Future Expansion

Future expansion may include:

  • Empty unit spaces
  • Prepared plug-in spaces
  • Spare starter buckets
  • Future VFD sections
  • Extended horizontal bus
  • Future vertical sections
  • Spare communication ports
  • Additional PLC I/O
  • Larger wireways
  • Reserved floor space
  • Future incoming or tie section

Clarify whether “spare” means:

  • Blank space only
  • Unit support installed
  • Vertical bus available
  • Power stabs prepared
  • Field wiring terminals installed
  • Complete spare bucket supplied
  • Future section bus extension provided

These options have different costs and certification implications.

Future expansion is easier when the original bus rating, section layout, wireways, network capacity, and room arrangement already account for it.


Step 20: Coordinate Shipping, Handling, and Installation

Large MCC lineups may need to be divided into shipping blocks.

The buyer should provide:

  • Maximum shipping width
  • Maximum shipping height
  • Maximum shipping weight
  • Door and corridor dimensions
  • Elevator dimensions
  • Crane or forklift access
  • Final equipment-room location
  • Foundation or housekeeping-pad details
  • Seismic requirements
  • Site bus-splice responsibility
  • Field wiring responsibility

The horizontal bus and ground bus must be properly reconnected across shipping splits.

Manufacturer documentation typically supplies layout drawings, installation instructions, handling information, wiring diagrams, test reports, and shipping-block information with assembled MCCs.

The installation path should be reviewed before the final lineup is approved.


Step 21: Define Documentation Requirements

A complete MCC project may require:

  • General arrangement drawing
  • One-line diagram
  • MCC elevation
  • Motor and feeder schedule
  • Unit layout
  • Busbar arrangement
  • Cable-entry drawing
  • Terminal plan
  • Control schematics
  • Unit wiring diagrams
  • Interconnection diagrams
  • PLC I/O list
  • Communication architecture
  • Network-address schedule
  • Protection settings
  • VFD parameter list
  • Nameplate schedule
  • Bill of materials
  • Spare-parts list
  • Factory test records
  • Installation instructions
  • Operation and maintenance manual
  • Certification documentation
  • Packing list

Current MCC manufacturer documentation packages may include elevation drawings, one-line diagrams when requested, unit wiring diagrams, spare-parts lists, manuals, and test reporting.

The required format, language, revision process, and approval timeline should be established before engineering begins.


Step 22: Define Factory Testing

Factory testing may include:

  • Visual inspection
  • Dimensional verification
  • Nameplate verification
  • Bus and ground continuity checks
  • Wiring verification
  • Mechanical interlock testing
  • Starter functional testing
  • Overload setting verification
  • Breaker trip-setting verification
  • VFD or soft-starter functional checks
  • Communication testing
  • PLC I/O testing
  • Metering verification
  • Control-power checks
  • Insulation or dielectric testing as applicable
  • Customer witness test

For an intelligent MCC, factory configuration may include network addresses, motor data, protective settings, and verification of connected-device communications.

The specification should distinguish between:

  • Standard factory testing
  • Functional testing
  • Factory acceptance testing
  • Customer witness testing
  • Integrated system testing
  • Site commissioning
Typical 480V three-phase MCC bucket showing motor power circuit, MCP, contactor, overload relay, control transformer, start-stop circuit, and grounding.

UL845 MCC RFQ Information Summary

CategoryInformation Required
System positionUpstream source and downstream motor loads
Electrical systemVoltage, phase, frequency, wire and grounding system
Motor listTag, HP/kW, FLA, duty, starting method and control
Main busRating, material, neutral and ground requirements
Incoming deviceMain lugs, breaker, fused switch, or multiple sources
Fault currentAvailable fault current and required complete MCC SCCR
Motor unitsStarter, reversing, soft starter, VFD, or feeder
Unit constructionFixed, plug-in, removable, or frame-mounted
Control systemLocal, hardwired, PLC, DCS, or SCADA
Control voltageAC or DC control-power requirements
CommunicationProtocol, topology, addressing and cybersecurity
CablesSize, quantity, entry direction and termination
EnvironmentIndoor, outdoor, temperature, moisture and corrosion
SafetyArc-flash mitigation or arc-resistant requirements
ExpansionSpare spaces, buckets, bus and future sections
InstallationAccess route, shipping blocks and room dimensions
DocumentationDrawings, schedules, test reports and manuals
ComplianceUL845, CSA, NRTL, field evaluation or project pathway

How E-abel Supports UL845-Related MCC Projects

For North American motor-control projects, customers may need coordinated support across enclosure structure, unit layout, busbar planning, control wiring, thermal management, documentation, and production.

Depending on the project scope and required certification pathway, E-abel can support:

  • UL845-related MCC project discussions
  • One-line diagram and motor-list review
  • Main and feeder requirement review
  • Floor-standing multi-section enclosure engineering
  • Incoming, starter, VFD, soft-starter, feeder, and PLC section planning
  • Fixed and removable-unit structural discussions
  • Busbar and grounding-layout coordination
  • Horizontal and vertical wireway planning
  • Cable-entry and terminal-space review
  • Control schematic and wiring coordination
  • Intelligent communication-layout discussions
  • Indoor and outdoor enclosure engineering
  • Powder-coated steel and stainless-steel manufacturing
  • Condensation-control and thermal-management planning
  • Standardized 3D design-library support
  • Customized 3D drawings for qualified projects
  • Assembly, wiring, labeling, testing, packing, and shipping coordination
  • CSA, ETL, field evaluation, or other third-party compliance pathway discussions where applicable

The exact certification status must be confirmed for the complete MCC configuration.

E-abel should not describe an assembly as UL845 listed solely because it contains UL-listed breakers, starters, overload relays, drives, or control devices.

The complete MCC must follow the applicable evaluated structure, bus system, unit combinations, component conditions, markings, manufacturing controls, testing, and certification pathway.

For some projects, E-abel’s appropriate role may be:

  • MCC enclosure manufacturer
  • Structural cabinet engineering partner
  • Busbar and unit-layout coordination partner
  • Assembly and wiring supplier
  • UL508A control-panel supplier for the associated process-control system
  • Production partner working with an authorized certification organization or listed MCC platform

Correctly defining this role during the RFQ stage reduces compliance risk and prevents confusion between an MCC, control panel, and custom multi-motor cabinet.

Engineering Recommendation

A reliable MCC begins with a complete motor list and system study.

Before cabinet design begins, the buyer should define:

  • System voltage and grounding
  • Main bus rating
  • Available fault current
  • Complete MCC SCCR
  • Motor horsepower and full-load current
  • Starting and speed-control methods
  • Starter and overload combinations
  • Fixed or removable units
  • Control voltage
  • PLC and communication architecture
  • Cable entry and wireway requirements
  • Indoor or outdoor environment
  • Arc-flash strategy
  • Maintenance and spare-unit plan
  • Future expansion
  • Certification pathway
  • Documentation and testing

The MCC layout should then be developed around these requirements.

When the motor list, one-line diagram, fault-current data, control philosophy, communication architecture, installation environment, and compliance expectations are clear, the manufacturer can develop a more accurate section layout, unit schedule, quotation, drawing package, and production plan.

 

UL845 Motor Control Center Specification Checklist

Before requesting a UL845 motor control center quotation, the buyer should prepare a complete electrical, motor, control, communication, installation, and compliance specification.

A useful MCC specification should allow the engineering team to determine:

  • Whether the equipment is correctly classified as an MCC
  • Main and vertical bus ratings
  • Incoming-device configuration
  • Complete assembly SCCR
  • Motor branch-circuit combinations
  • Starter, soft-starter, and VFD requirements
  • Unit sizes and section arrangement
  • Fixed or removable unit construction
  • Wireway and cable-termination space
  • Intelligent communication architecture
  • Thermal-management requirements
  • Maintenance and expansion provisions
  • Required testing and documentation
  • Applicable certification pathway

UL845 applies to motor control centers intended for use under the applicable U.S., Canadian, and Mexican installation frameworks. Its published scope includes qualifying MCCs used on circuits with available short-circuit current up to 200,000 A under the stated conditions, but this does not mean every MCC automatically carries that rating. The final voltage, current, and SCCR must appear within the evaluated and marked configuration of the specific assembly.


1. Basic Project Information

☐ Project name

☐ Installation location

☐ Country, state, province, or territory

☐ Industrial sector

☐ New construction, replacement, retrofit, or expansion

☐ Indoor or outdoor installation

☐ Required delivery date

☐ Expected service life

☐ One-time project or repeat production

☐ Required certification or evaluation pathway

☐ Owner-approved component brands

☐ Utility and local authority requirements

Typical MCC application sectors may include:

  • Water and wastewater treatment
  • Pump stations
  • Manufacturing
  • Automotive production
  • Food and beverage processing
  • Mining and metals
  • Oil and gas
  • Chemical processing
  • HVAC and cooling systems
  • Conveyors and material handling
  • Warehousing and logistics
  • Infrastructure projects

Commercial MCC platforms are designed to group motor control, automation, industrial communication, and certain distribution functions in one coordinated lineup.


2. Equipment Classification

Confirm whether the project actually requires:

☐ UL845 motor control center

☐ UL508A industrial control panel

☐ UL891 switchboard

☐ UL1558 low-voltage switchgear

☐ IEC 61439 assembly

☐ Standalone VFD panel

☐ Pump control panel

☐ Enclosure-only solution

A cabinet containing several starters is not automatically a UL845 MCC.

UL508A specifically excludes motor control centers, MCC sections, MCC units, and equipment intended for field installation into an MCC from its industrial-control-panel scope; those products fall under UL845.

A typical UL845 MCC normally includes:

  • One or more coordinated vertical sections
  • Common horizontal power bus
  • Section or vertical distribution bus
  • Repeated motor-control or feeder units
  • Defined wireways
  • Continuous grounding provisions
  • Evaluated unit combinations
  • Complete MCC markings

The equipment classification should be resolved before detailed cabinet design begins.


3. One-Line Diagram and System Position

Provide a current one-line diagram showing:

☐ Incoming power source

☐ Upstream transformer

☐ Upstream switchboard or switchgear

☐ Upstream feeder protective device

☐ MCC main device

☐ Horizontal main bus

☐ Motor feeders

☐ Nonmotor feeders

☐ Generators or alternate sources

☐ Transfer equipment

☐ Tie devices

☐ Grounding arrangement

☐ Downstream control panels

☐ Future expansion

A typical system arrangement may be:

Utility or transformer → UL891 switchboard or UL1558 switchgear → UL845 MCC → Motors and motor-driven equipment

The MCC’s position affects:

  • Main-device requirements
  • Main-bus rating
  • SCCR
  • Grounding and neutral configuration
  • Cable entry
  • Metering
  • Source interlocking
  • Service-equipment requirements

4. Electrical System Information

Provide:

☐ Nominal voltage

☐ Single-phase, three-phase, or DC system

☐ Frequency

☐ Three-wire or four-wire arrangement

☐ Grounded, ungrounded, or resistance-grounded system

☐ Neutral requirement

☐ Control voltage

☐ Auxiliary power voltage

☐ External or internal control-power source

The electrical-system description should be complete.

For example:

  • 480V, three-phase, three-wire, 60Hz
  • 480Y/277V, three-phase, four-wire, 60Hz
  • 600V, three-phase, three-wire, 60Hz
  • Project-specific DC system

UL845’s current scope covers qualifying AC and DC MCCs within its stated voltage and application boundaries, but available configurations remain dependent on the certified MCC platform.


5. Complete Motor List

Provide one line of data for every motor.

Motor DataInformation Required
Equipment identificationMotor or process tag
Load descriptionPump, fan, conveyor, compressor, mixer, or other load
Motor outputHorsepower or kilowatt rating
Full-load currentMotor nameplate or engineering value
Voltage and phaseComplete motor electrical rating
DutyContinuous, intermittent, standby, or emergency
Starting methodAcross-the-line, reversing, soft starter, VFD, or other
Speed requirementFixed speed, two speed, or variable speed
Control sourceLocal, PLC, DCS, SCADA, or building automation
FeedbackRun, trip, available, current, speed, fault
Cable informationSize, quantity, type, shielding, and length
Expansion requirementInstalled spare, spare bucket, or future space

Also provide, where applicable:

☐ Motor efficiency class

☐ Service factor

☐ Locked-rotor current

☐ Starts per hour

☐ Acceleration time

☐ Load torque characteristic

☐ Reversing requirement

☐ Motor brake

☐ Winding heater

☐ Motor temperature sensors

☐ Bearing temperature sensors

☐ Emergency-stop requirement

☐ Local disconnect requirement

☐ Hazardous-location information

Motor horsepower alone is not enough to select the breaker, starter, overload relay, VFD, unit size, control transformer, conductor, or SCCR combination.


6. Main Bus and Distribution Bus

Specify:

☐ Horizontal main-bus ampere rating

☐ Vertical bus rating

☐ Copper or aluminum bus

☐ Bus plating requirement

☐ Neutral bus, where required

☐ Continuous ground bus

☐ Future bus extension

☐ Shipping-split bus connections

☐ Bus short-circuit bracing

☐ Temperature-rise requirements

The bus rating should consider:

  • Simultaneous motor operation
  • Motor full-load currents
  • Demand and diversity
  • Nonmotor feeders
  • Continuous loads
  • Starting conditions
  • VFD and soft-starter loads
  • Future motors
  • Spare units
  • Upstream transformer capacity

UL845 MCC platforms are constructed as coordinated free-standing sections connected through continuous bus and grounding systems; manufacturer selection guides treat horizontal bus, vertical bus, grounding, SCCR, and section configuration as related design inputs.


7. Incoming Configuration

Select the required incoming arrangement.

☐ Main lugs only

☐ Main circuit breaker

☐ Fusible main switch

☐ Main disconnect

☐ Dual incoming sources

☐ Main-tie-main arrangement

☐ Normal and emergency sources

☐ Transfer equipment

☐ Adjacent transformer connection

For a main breaker, provide:

  • Frame rating
  • Trip rating
  • Number of poles
  • Interrupting rating
  • Trip-unit functions
  • Ground-fault protection
  • Shunt trip
  • Undervoltage release
  • Auxiliary contacts
  • Communication requirement
  • Fixed or removable construction

For a main-lug-only MCC, identify the upstream protective device and its rating.

For multiple-source systems, define:

  • Normal source
  • Emergency source
  • Source priority
  • Permitted operating combinations
  • Transfer sequence
  • Tie-device logic
  • Mechanical and electrical interlocking
  • Parallel-operation restrictions
  • Load-shedding requirements

8. Available Fault Current and SCCR

Provide:

☐ Available RMS symmetrical fault current

☐ System voltage

☐ Transformer impedance

☐ Utility fault contribution

☐ Generator contribution

☐ Motor contribution

☐ Parallel-source operating modes

☐ Future source contribution

☐ Required complete-MCC SCCR

The following ratings should not be treated as interchangeable:

  • Main-breaker interrupting rating
  • Individual starter SCCR
  • VFD input rating
  • Motor circuit protector rating
  • Bus rating
  • Complete MCC SCCR

A combination motor controller may include a disconnecting means, overcurrent protective device, motor controller, and motor overload protection. Any higher combination SCCR depends on the exact approved components and stated conditions—not merely the strongest individual component.

Confirm the required SCCR before the unit schedule and component selections are finalized.


9. Motor Starting and Speed-Control Methods

For each motor, select:

☐ Across-the-line starter

☐ Reversing starter

☐ Two-speed starter

☐ Reduced-voltage starter

☐ Soft starter

☐ Variable frequency drive

☐ Feeder-only unit

The selection should consider:

  • Motor full-load current
  • Starting current
  • Required starting torque
  • Acceleration time
  • Starts per hour
  • Process-flow requirements
  • Mechanical stress
  • Utility limitations
  • Required speed range
  • Energy objective
  • Harmonic impact
  • Bypass requirement
  • Maintenance strategy

Motor starters are used to start, stop, reverse, and protect motors; the selected method should match the motor and process rather than simply using the smallest available unit.


10. Motor Branch-Circuit Components

For every motor unit, define:

☐ Circuit breaker

☐ Motor circuit protector

☐ Fusible disconnect

☐ Contactor

☐ Overload relay

☐ Soft starter

☐ VFD

☐ Control transformer

☐ Branch-circuit protection

☐ Control-circuit protection

☐ Terminal blocks

☐ Auxiliary relays

☐ Local controls

☐ Communication modules

The motor branch circuit should provide the required functions for:

  1. Disconnecting
  2. Short-circuit and ground-fault protection
  3. Motor control
  4. Motor overload protection

Individual devices used for starting, stopping, regulating, controlling, or protecting motors may be covered under component standards such as UL508, while UL845 applies to the complete coordinated MCC assembly.


11. Overload-Protection Requirements

Specify:

☐ Thermal overload relay

☐ Electronic overload relay

☐ Intelligent motor-protection relay

☐ VFD-based motor protection

☐ Soft-starter protection

☐ Manual or automatic reset

☐ Overload trip class

☐ Phase-loss protection

☐ Phase-imbalance protection

☐ Stall or jam protection

☐ Ground-fault monitoring

☐ Motor thermal model

☐ Trip-history recording

The overload setting should be based on:

  • Motor nameplate current
  • Service factor
  • Motor duty
  • Ambient conditions
  • Starting time
  • Applicable engineering requirements
  • Manufacturer instructions

The overload relay setting should not simply be copied from the upstream breaker rating.


12. Unit Construction

Select:

☐ Fixed unit

☐ Plug-in unit

☐ Removable unit

☐ Frame-mounted unit

☐ Product-specific withdrawable arrangement

Clarify whether the project requires:

  • Unit removal after complete de-energization
  • Closed-door isolation
  • Disconnect or test position
  • Separable control connectors
  • Automatic bus shutters
  • Standardized replacement buckets
  • Remote unit operation
  • Spare-unit interchangeability

Plug-in units may improve replacement and expansion, but they are not automatically interchangeable and are not automatically safe to remove while the MCC remains energized.

The replacement unit must match the applicable:

  • MCC platform
  • Unit dimensions
  • Power-stab rating
  • Motor rating
  • Control voltage
  • SCCR
  • Control connector
  • Communication architecture
  • Door and interlock system
  • Approved component combination

Rockwell’s UL845 MCC platform, for example, distinguishes between plug-in units and frame-mounted units and uses platform-specific labeling and construction requirements.


13. Unit and Section Layout

Provide requirements for:

☐ Main incoming section

☐ Starter sections

☐ VFD sections

☐ Soft-starter sections

☐ Feeder sections

☐ PLC or remote-I/O section

☐ Communication section

☐ Metering section

☐ Control-power section

☐ Spare unit spaces

☐ Future vertical sections

The elevation drawing should show:

  • Section identification
  • Unit tags
  • Unit sizes
  • Unit positions
  • Main and feeder devices
  • Horizontal and vertical wireways
  • Bus location
  • Spare spaces
  • VFD ventilation
  • Shipping splits
  • Cable-entry direction
  • Overall dimensions

Current UL845 MCC platforms use free-standing modular sections that may be factory assembled into shipping blocks with continuous power-bus and grounding connections.


14. VFD Requirements

For each drive unit, specify:

☐ Motor horsepower or kilowatt rating

☐ Motor full-load current

☐ Drive-duty rating

☐ Input voltage

☐ Output frequency range

☐ Speed-reference source

☐ Communication protocol

☐ Bypass requirement

☐ Input disconnect

☐ Input protection

☐ Line reactor

☐ Harmonic filter

☐ Output reactor

☐ dV/dt filter

☐ Sine-wave filter

☐ Braking resistor

☐ Regenerative function

☐ Motor cable length

☐ Shielding and grounding requirements

☐ Enclosure ventilation

☐ Ambient temperature and altitude

For a lineup containing multiple drives, review:

  • Total heat loss
  • Harmonic distortion
  • Transformer loading
  • Generator compatibility
  • Power-factor correction
  • Forced ventilation
  • Drive derating
  • Communication architecture

A VFD compartment cannot be sized only by motor horsepower. Thermal conditions, cable length, filters, bypass devices, harmonics, and maintenance access can significantly affect the required unit size.


15. Soft-Starter Requirements

Specify:

☐ Motor rating

☐ Starting-current limit

☐ Starting ramp time

☐ Stopping ramp time

☐ Pump-control function

☐ Internal or external bypass

☐ Number of starts per hour

☐ Overload functions

☐ Communication

☐ Local bypass requirement

☐ Ambient conditions

A soft starter may reduce starting current and mechanical stress, but it does not normally provide the same continuous speed-control capability as a VFD.


16. Control Philosophy

For every motor, define:

☐ Local manual control

☐ Remote hardwired control

☐ PLC control

☐ DCS control

☐ SCADA control

☐ Building automation control

☐ Automatic sensor-based operation

☐ Local/remote selector

☐ Hand-off-auto control

Define the required signals:

  • Start command
  • Stop command
  • Emergency stop
  • Run feedback
  • Trip feedback
  • Available status
  • Local/remote status
  • Motor current
  • Speed feedback
  • Fault reset
  • Permissives
  • Process interlocks
  • Bypass status

The specification should state which system has final command authority and what happens when:

  • Communication is lost
  • PLC power is lost
  • A permissive is removed
  • Emergency stop is activated
  • Local control is selected
  • A motor trips
  • Power returns after an outage

17. Control Power

Specify:

☐ 120V AC control power

☐ 24V DC control power

☐ Other project-specific voltage

☐ Individual unit control transformers

☐ Common MCC control transformer

☐ External control-power source

☐ UPS-supported control power

☐ Redundant DC power supplies

Calculate the required capacity for:

  • Contactor coils
  • Relays
  • Solenoids
  • Pilot lights
  • PLC and remote I/O
  • Communication switches
  • Meters
  • Operator interfaces
  • Spare capacity

Provide primary and secondary protection requirements for control transformers and power supplies.


18. Intelligent MCC and Communication

Specify:

☐ Conventional hardwired MCC

☐ Intelligent MCC

☐ Networked overload relays

☐ Networked VFDs

☐ Networked soft starters

☐ Power metering

☐ Motor diagnostics

☐ Remote monitoring

☐ Predictive-maintenance data

Potential monitored information includes:

  • Current
  • Voltage
  • Power
  • Energy
  • Run status
  • Trip status
  • Thermal capacity
  • Start count
  • Running hours
  • Fault history
  • Drive speed
  • Device health
  • Maintenance alerts

Eaton defines an intelligent MCC as a motor-control assembly integrated with communications and smart devices to provide actionable data for facility, process, and power-system decisions.

Also define:

  • Protocol
  • Network topology
  • Device-address strategy
  • Copper or fiber network
  • Ethernet-switch location
  • Redundant-network requirement
  • PLC or DCS interface
  • SCADA tags
  • Time synchronization
  • Remote-access permissions
  • Cybersecurity responsibility
  • Communication-loss behavior
  • Factory configuration scope

19. Wireways and Cable Termination

Provide:

☐ Top cable entry

☐ Bottom cable entry

☐ Front termination

☐ Rear termination

☐ Conduit entry

☐ Cable-tray entry

☐ Motor cable sizes

☐ Number of conductors

☐ Ground conductor size

☐ VFD cable type

☐ Shielding requirement

☐ Control cable quantity

☐ Communication cable quantity

☐ Instrument cable separation

☐ Spare cable capacity

The cable design should account for:

  • Bending radius
  • Lug capacity
  • Cable support
  • Shield termination
  • Cable segregation
  • Electromagnetic interference
  • VFD output routing
  • Field-installation access
  • Future cables

An MCC may have sufficient bucket space but inadequate wireway capacity. Unit layout and cable routing must therefore be reviewed together.


20. Grounding and Bonding

Specify:

☐ Continuous horizontal ground bus

☐ Section grounding connections

☐ Unit grounding provisions

☐ Door bonding

☐ Motor-cable grounding terminals

☐ Ground-bus material

☐ Ground-bus sizing requirements

☐ Shipping-split ground connections

☐ Neutral bus, if required

The equipment grounding system must remain continuous through the complete lineup and across shipping splits.

The neutral bus, when required, is electrically distinct from the equipment grounding bus except at the specific bonding point defined by the system design.


21. Installation Environment

Identify:

☐ Indoor electrical room

☐ Outdoor installation

☐ Dust

☐ Dripping liquid

☐ Humidity

☐ Condensation

☐ Direct rain

☐ Solar exposure

☐ Coastal salt

☐ Chemical vapors

☐ Wastewater gases

☐ High or low ambient temperature

☐ High altitude

☐ Washdown environment

☐ Hazardous location

Specify the required enclosure type and environmental protection.

For outdoor or humid locations, consider:

  • Weather-resistant roof
  • Space heaters
  • Thermostats or humidistats
  • Condensation drainage
  • Sealed cable entry
  • Corrosion-resistant coating
  • Stainless-steel construction
  • Rain-protected ventilation
  • Cooling or heat exchange
  • Walk-in or non-walk-in outer structure

The environmental rating must apply to the complete assembly. Placing an indoor MCC inside a generic outdoor enclosure does not automatically establish an outdoor UL845 certification.


22. Arc-Flash Risk Reduction

Specify any required measures:

☐ Current-limiting protection

☐ Energy-reducing maintenance mode

☐ Zone-selective interlocking

☐ Remote operation

☐ Remote monitoring

☐ Closed-door unit isolation

☐ Automatic vertical-bus shutters

☐ Infrared inspection windows

☐ Arc-detection system

☐ Remote racking

☐ Arc-containment or arc-resistant construction

UL845 certification alone does not establish arc-resistant performance.

Some manufacturers offer separately engineered arc-containment or arc-resistant MCC options. The applicable test basis, accessibility classification, bus rating, enclosure configuration, venting system, operating condition, and installation restrictions must be confirmed for the specific product. Rockwell’s own specification material notes that arc-resistant MCC terminology and evaluation must be treated separately from basic UL845 compliance.


23. Maintenance and Spare Strategy

Define:

☐ Planned shutdown frequency

☐ Preventive-maintenance interval

☐ Spare starter buckets

☐ Spare contactors

☐ Spare overload relays

☐ Spare breakers or fuses

☐ Spare VFDs

☐ Spare communication modules

☐ Off-site unit repair

☐ Infrared inspection requirement

☐ Condition monitoring

☐ Obsolescence plan

A spare bucket should match:

  • MCC platform
  • Unit size
  • Starter or drive rating
  • Breaker or fuse configuration
  • Overload range
  • Control voltage
  • Control connector
  • Communication module
  • SCCR
  • Door and interlock arrangement
  • Motor application

Retrofit units intended for field installation into existing MCCs may require their own evaluation for compatibility with the specified MCC platform.


24. Future Expansion

Specify:

☐ Blank unit spaces

☐ Prepared plug-in positions

☐ Spare starter units

☐ Spare feeder units

☐ Future VFD sections

☐ Extended main bus

☐ Future vertical section

☐ Spare network ports

☐ Spare PLC I/O

☐ Additional wireway capacity

☐ Reserved floor space

Clarify whether “spare” means:

  • Empty space only
  • Unit support installed
  • Vertical bus available
  • Power connection prepared
  • Control wiring prepared
  • Complete spare bucket supplied
  • Future section bus extension provided

These options have different cost, engineering, and certification implications.


25. Shipping and Installation

Provide:

☐ Maximum shipping width

☐ Maximum shipping height

☐ Maximum shipping weight

☐ Door and corridor dimensions

☐ Elevator dimensions

☐ Forklift access

☐ Crane access

☐ Equipment-room layout

☐ Housekeeping-pad dimensions

☐ Seismic requirements

☐ Shipping-block limits

☐ Field bus-splice responsibility

☐ Field wiring responsibility

UL845 MCC lineups may be assembled into multiple shipping blocks, with the horizontal power bus and grounding system reconnected during site installation.

The installation route should be confirmed before the final lineup drawing is approved.


26. Documentation

Specify the required documents:

☐ General arrangement drawing

☐ One-line diagram

☐ MCC elevation

☐ Motor and feeder schedule

☐ Unit layout

☐ Bus arrangement

☐ Cable-entry drawing

☐ Terminal plan

☐ Control schematic

☐ Unit wiring diagrams

☐ Interconnection diagrams

☐ PLC I/O list

☐ Communication architecture

☐ Network-address schedule

☐ Breaker and overload settings

☐ VFD parameter list

☐ Nameplate schedule

☐ Bill of materials

☐ Spare-parts list

☐ Factory test records

☐ Installation manual

☐ Operation and maintenance manual

☐ Certification documentation

Also confirm:

  • Drawing language
  • File format
  • Approval stages
  • Revision schedule
  • Final as-built requirements
  • Customer document numbering

27. Factory Testing

Define whether the project requires:

☐ Standard production testing

☐ Functional testing

☐ Factory acceptance test

☐ Customer witness test

☐ Integrated control-system test

☐ Site acceptance test

Possible factory checks include:

  • Visual and dimensional inspection
  • Nameplate verification
  • Bus and ground continuity
  • Wiring verification
  • Mechanical interlock testing
  • Starter operation
  • Overload-setting verification
  • Breaker-setting verification
  • VFD functional checks
  • Soft-starter checks
  • Metering verification
  • Communication testing
  • PLC I/O testing
  • Control-power verification
  • Dielectric or insulation testing where applicable
  • Alarm and feedback testing

For intelligent MCCs, factory testing may also include device-address configuration, motor data, communication checks, protection settings, and software validation.

Quick MCC RFQ Summary

CategoryMinimum Information
SystemOne-line diagram, voltage, phase, frequency, and grounding
MotorsComplete motor list with HP/kW, FLA, duty, and starting method
Main distributionMain bus rating and incoming-device arrangement
Fault currentAvailable fault current and required complete-MCC SCCR
Motor unitsStarter, reversing starter, soft starter, VFD, or feeder
Unit typeFixed, plug-in, removable, or frame-mounted
ControlControl voltage, logic, permissives, feedback, and ownership
CommunicationProtocol, topology, addressing, and cybersecurity
CablesSizes, quantities, shielding, entry, and termination
EnvironmentIndoor/outdoor conditions, temperature, moisture, and corrosion
SafetyArc-flash mitigation and any special containment requirement
ExpansionSpare units, bus capacity, network ports, and future sections
InstallationRoom layout, access route, shipping blocks, and foundations
DocumentsDrawings, schedules, testing, manuals, and approval requirements
ComplianceUL845 or applicable CSA, NRTL, or field-evaluation pathway

FAQ:

1. What is a UL845 motor control center?

A UL845 motor control center is a coordinated low-voltage assembly used to distribute, protect, start, stop, control, and monitor multiple motors and related loads.

It typically contains interconnected vertical sections, horizontal and vertical busbars, grounding systems, wireways, and motor-control or feeder units.

UL845 is the North American product standard specifically covering motor control centers under the installation frameworks identified in its scope.

2. What is an MCC bucket?

An MCC bucket is the commonly used industry term for an individual motor-control or feeder unit installed within an MCC section.

A typical bucket may contain:

  • Disconnecting means
  • Circuit breaker or motor circuit protector
  • Contactor
  • Overload relay
  • Control transformer
  • Terminal blocks
  • Local controls
  • Communication device

The formal term used by a manufacturer may be “unit” rather than “bucket.”

3. Is every bucket removable?

No.

MCC units may be:

  • Fixed
  • Plug-in
  • Removable
  • Frame-mounted
  • Product-specific withdrawable designs

Large VFDs, soft starters, main devices, and special control assemblies are often fixed or frame-mounted because of their dimensions and weight.

4. Can an MCC unit be removed while the bus remains energized?

This should never be assumed.

The permitted procedure depends on the specific MCC platform, unit design, disconnect position, shutters, interlocks, manufacturer instructions, arc-flash conditions, and facility safety procedures.

Plug-in construction describes the connection method; it does not automatically authorize energized removal.

5. What is the difference between an MCC and a UL508A control panel?

A UL845 MCC normally uses common horizontal and vertical power buses with repeated motor-control units for multiple motors.

A UL508A industrial control panel normally controls a machine or process using PLCs, relays, contactors, drives, terminals, and control wiring within a panel enclosure.

A UL508A panel may control several motors, but that does not automatically make it a UL845 MCC. UL508A formally excludes motor control centers and MCC units from its product scope.

6. What is the difference between an MCC and a switchboard?

A UL891 switchboard primarily distributes power to multiple feeders and downstream equipment.

A UL845 MCC primarily distributes, protects, starts, stops, and controls multiple motors.

A common arrangement is:

Switchboard → MCC → Motors

An MCC may contain some nonmotor feeder units, but it should not automatically replace a switchboard when the project is primarily general power distribution.

7. What is the difference between an MCC and switchgear?

UL1558 switchgear generally provides major system distribution and protection through low-voltage power circuit breakers.

A UL845 MCC provides motor-level distribution and control through starters, overload relays, VFDs, soft starters, and feeder units.

A large facility may use switchgear to feed several process MCCs.

8. Can an MCC contain VFDs?

Yes.

An MCC can integrate VFD units for pumps, fans, conveyors, compressors, and other variable-speed loads.

The design must account for:

  • Heat loss
  • Ventilation
  • Harmonics
  • Motor cable length
  • Output filters
  • Line reactors
  • Bypass devices
  • Ambient temperature
  • Communication
  • Maintenance access

A VFD unit may occupy more space than a conventional starter bucket.

9. Can an MCC contain soft starters?

Yes.

Soft starters are commonly integrated where controlled acceleration, reduced starting current, or reduced mechanical stress is required without continuous speed control.

The specification should define starting time, current limit, number of starts per hour, bypass, stopping requirements, and communication.

10. What is the difference between a circuit breaker and an overload relay in an MCC?

The circuit breaker or motor circuit protector is part of the short-circuit and ground-fault protection arrangement.

The overload relay protects the motor against sustained overload and related abnormal operating conditions.

These devices perform different functions and should not be substituted for one another.

11. How is an MCC SCCR determined?

The complete MCC SCCR depends on the evaluated combination of:

  • Main and branch protective devices
  • Disconnecting means
  • Motor controllers
  • Overload devices
  • VFD or soft-starter input protection
  • Bus structure
  • Unit construction
  • Complete assembly configuration

The rating of one breaker or contactor does not automatically establish the complete MCC rating. UL publishes specific combination motor-controller SCCR information based on approved groups of components and stated conditions.

12. Is the 200 kA value in UL845 the rating of every MCC?

No.

The standard’s published scope addresses MCCs used on circuits with available short-circuit current not exceeding 200,000 A under the scope conditions.

Each actual MCC must still carry a marked SCCR based on its evaluated construction and component combinations, and that rating may be lower.

13. What is an intelligent MCC?

An intelligent MCC integrates networked protective devices, starters, VFDs, soft starters, meters, and communication equipment.

It may provide:

  • Motor status
  • Current and power information
  • Trip history
  • Running hours
  • Thermal information
  • Fault diagnostics
  • Remote monitoring
  • Predictive-maintenance data

The intelligence layer improves information and integration, but it does not replace the PLC, process logic, electrical protection, functional-safety system, or cybersecurity architecture.

14. Can an intelligent MCC operate without a PLC?

Individual units may support local or basic automatic functions, but an intelligent MCC does not automatically replace a PLC or DCS.

Complex process sequencing, permissives, interlocks, production logic, alarm management, and system-level decisions usually remain within the process-control system.

15. Is a UL845 MCC automatically arc-resistant?

No.

UL845 is the product standard for motor control centers, but it does not by itself establish arc-resistant or arc-containment performance.

Any such claim must be tied to a separately engineered and tested manufacturer configuration, with defined ratings, doors, sections, venting, installation conditions, and operating procedures.

16. Can a UL845 MCC be installed outdoors?

Yes, when the specific evaluated MCC platform includes the required outdoor construction and environmental rating.

Outdoor applications may also need:

  • Weather-resistant roof construction
  • Space heaters
  • Condensation control
  • Sealed cable entry
  • Corrosion protection
  • Rain-protected ventilation
  • Stainless-steel or coated external structures

Placing an indoor MCC inside an unrelated outdoor enclosure does not automatically make the complete assembly an outdoor UL845-listed MCC.

17. Is UL845 equivalent to IEC 61439?

No.

UL845 is a North American product standard specifically for motor control centers.

IEC 61439 is an international assembly framework that may cover motor-control functional units as part of a low-voltage power switchgear and controlgear assembly.

The standards use different component systems, verification processes, markings, terminology, and market-access pathways.

18. Can an IEC MCC be converted to UL845?

It may be possible to develop a dual-market or redesigned platform, but a completed IEC MCC cannot normally be treated as UL845 compliant merely by changing labels or replacing a few components.

The conversion may affect:

  • Breakers and starters
  • SCCR
  • Bus construction
  • Clearances
  • Wire types
  • Component certifications
  • Grounding
  • Unit combinations
  • Markings
  • Testing
  • Production controls

A dual-standard objective should be identified at the beginning of the project.

19. Are UL-listed components enough to make a UL845 MCC?

No.

Listed breakers, contactors, drives, overload relays, terminals, and control devices do not automatically establish certification of the complete MCC.

The assembly must follow the applicable evaluated MCC design, bus structure, unit combinations, ratings, construction requirements, markings, manufacturing controls, and certification process.

20. Can an existing MCC be modified in the field?

Field modifications may affect:

  • SCCR
  • Bus loading
  • Unit compatibility
  • Ventilation
  • Interlocks
  • Grounding
  • Enclosure rating
  • Certification
  • Documentation

Modifications should be reviewed by the MCC manufacturer, qualified engineering team, certification organization, and authority having jurisdiction as applicable.

UL Solutions offers field-evaluation services for customized or modified electrical equipment when project circumstances require an on-site compliance pathway.

21. What information is needed to quote an MCC?

At minimum, provide:

  • One-line diagram
  • Complete motor list
  • System voltage and grounding
  • Main-bus rating
  • Available fault current
  • Required MCC SCCR
  • Incoming-device requirement
  • Motor starting methods
  • Unit construction
  • Control voltage
  • PLC and communication architecture
  • Cable-entry information
  • Installation environment
  • Expansion requirements
  • Certification expectations
  • Documentation and testing requirements

Without these details, the supplier can provide only a preliminary concept.

Conclusion

A UL845 motor control center is a coordinated electrical system for the centralized distribution, protection, starting, stopping, speed control, monitoring, and maintenance of multiple motors.

A typical MCC may combine:

  • Main incoming devices
  • Horizontal and vertical busbars
  • Combination motor starters
  • Overload relays
  • Soft starters
  • Variable frequency drives
  • Feeder breakers
  • Control transformers
  • PLC and remote-I/O equipment
  • Intelligent communication
  • Fixed or removable motor-control units
  • Horizontal and vertical wireways
  • Grounding and bonding systems

The MCC should not be treated as an empty metal lineup that can be filled with any available motor-control components.

Its performance depends on the coordination of:

  • Electrical-system requirements
  • Motor data
  • Main and vertical bus loading
  • Available fault current
  • Complete assembly SCCR
  • Starter and protective-device combinations
  • Unit construction
  • Cable routing
  • Thermal management
  • Communication architecture
  • Environmental conditions
  • Maintenance strategy
  • Certification requirements

The most important design input is the motor list.

Before layout begins, the engineering team should know:

  • What motors are connected?
  • What is each motor’s full-load current?
  • How should each motor start?
  • Does it require reversing or speed control?
  • What fault current is available?
  • What control system operates it?
  • What data must be communicated?
  • How will the unit be maintained?
  • What future expansion is expected?
  • What complete assembly certification is required?

Once these questions are answered, the main bus, unit sizes, section quantity, wireways, starter combinations, drive thermal management, communication system, and overall dimensions can be developed accurately.

A correctly specified UL845 MCC can provide:

  • Centralized motor control
  • Organized power distribution
  • Improved maintenance
  • Modular expansion
  • Reduced field wiring
  • Consistent motor protection
  • Intelligent monitoring
  • Better integration with plant automation

A poorly specified MCC may create:

  • Undersized busbars
  • Inadequate SCCR
  • Incorrect starter combinations
  • Insufficient wireway space
  • Excessive VFD heat
  • Communication conflicts
  • Difficult maintenance
  • Certification problems
  • Costly project redesign

The engineering specification should therefore come before the cabinet drawing.

How E-abel Supports UL845-Related MCC Projects

For North American motor-control projects, E-abel can support early equipment-classification discussions, enclosure engineering, section arrangement, wiring coordination, and manufacturing planning.

Depending on the project scope and required compliance pathway, E-abel can support:

  • One-line diagram review
  • Motor-list review
  • UL845 MCC versus UL508A control-panel classification
  • Main incoming and bus-layout discussions
  • Starter, VFD, soft-starter, feeder, and PLC section planning
  • Fixed and removable unit structural concepts
  • Multi-section floor-standing enclosure engineering
  • Horizontal and vertical wireway planning
  • Cable-entry and termination-space review
  • Grounding and bonding layout coordination
  • Control-schematic and wiring support
  • Intelligent communication-layout discussions
  • VFD thermal-management planning
  • Indoor and outdoor enclosure engineering
  • Powder-coated steel and stainless-steel manufacturing
  • Condensation and corrosion-control solutions
  • Shipping-section planning
  • Standardized 3D design-library support
  • Customized 3D drawings for qualified projects
  • Assembly, wiring, labeling, testing, packing, and shipping coordination
  • CSA, ETL, field evaluation, or other third-party pathway discussions where applicable

The exact certification status must be confirmed for the final MCC configuration.

E-abel should not represent an assembly as UL845 listed merely because it contains UL-listed breakers, contactors, overload relays, VFDs, soft starters, or control components.

Depending on the project, E-abel’s role may be:

  • MCC enclosure manufacturer
  • Structural cabinet engineering partner
  • Busbar and unit-layout coordination partner
  • Assembly and wiring supplier
  • UL508A supplier for the associated process-control panel
  • Production partner working with an authorized MCC platform or certification organization

Clearly defining the manufacturing and certification responsibilities during the RFQ stage helps prevent misunderstandings between:

  • A UL845 MCC
  • A UL508A multi-motor control panel
  • A switchboard
  • A custom motor-control cabinet
  • An IEC MCC
  • An enclosure-only product

Related Reading

Continue exploring the E-abel North American Standards content cluster:

Recommended future supporting articles:

  • UL845 MCC vs UL508A Control Panel
  • NEMA MCC vs IEC MCC
  • How to Specify a Motor Control Center
  • VFD vs Soft Starter
  • Fixed vs Removable MCC Units
  • Intelligent Motor Control Centers Explained
  • Motor Control Center SCCR Explained
  • Outdoor Motor Control Center Design Guide

References

Final MCC engineering should use the current applicable standards, certified manufacturer documentation, project specifications, adopted electrical codes, safety requirements, and authority having jurisdiction expectations.

Primary reference areas include:

  • UL845 — Motor Control Centers
  • UL508 — Industrial Control Equipment
  • UL508A — Industrial Control Panels
  • UL489 — Molded-Case Circuit Breakers
  • UL60947-4-1 — Contactors and Motor Starters
  • UL61800-5-1 — Adjustable Speed Electrical Power Drive Systems
  • NEMA ICS 18 — Motor Control Centers
  • NFPA 70 — National Electrical Code
  • NFPA 70E — Electrical Safety in the Workplace
  • CSA C22.1 — Canadian Electrical Code
  • IEC 61439-1 and IEC 61439-2
  • IEC 60947-2
  • IEC 60947-4-1
  • IEC 60947-4-2
  • Certified manufacturer MCC selection, installation, and maintenance documentation

The active sixth edition of UL845 was published in February 2025. Its scope applies to MCCs intended for use under the stated U.S., Canadian, and Mexican installation frameworks and establishes the upper available-fault-current boundary addressed by the standard; actual product ratings remain dependent on the evaluated and marked assembly.

Soft CTA

Need help preparing a motor control center for a North American industrial project?

Share your one-line diagram, complete motor list, system voltage, main-bus requirement, available fault current, required SCCR, starting methods, VFD and soft-starter requirements, control philosophy, communication architecture, cable-entry information, installation environment, expansion plan, and certification expectations before final quotation.